7. AUXILIARY FUNCTION 
 
7.15 External forced stop disabled 
7.15.1 Summary 
The external forced stop disabled function disables the external forced stop by input signal (EMI) from the I/O 
connector. 
 
Note. Software forced stop by system command bit and forced stops due to system errors such as SSCNET 
communication errors (system status code E
h) are not disabled. 
 
 
7.15.2 Interface 
The interface added for the external forced stop disabled function is as follows. 
 
(1) System status bit 
Address Bit Abbreviation 
Signal 
name 
0452 0  EMIO During forced stop 
 1    Reserved 
 2 TSTO 
In test mode 
 3 
 
Reserved 
 4 
 5 
 6 EMID 
External forced stop disabled 
 7    Reserved
 
 
(2) System parameter 
 
Parameter No.  Abbreviation 
Name 
Initial value
Unit
Setting 
range 
Function 
000E *EMID 
External 
forced 
stop disabled 
0000h 
 
0000h to 
FFFFh 
Disable the forced stop by EMI signal. 
5AE1h 
: Forced stop disabled 
Other than 5AE1h  : Forced stop enabled 
 
 
7.15.3 Setting method 
To disable the external forced stop, set 5AE1h to external forced stop disabled (parameter No.000E), and start 
the system. When the external forced stop is disabled, external forced stop disabled signal (EMID) turns ON. 
 
Note 1. External forced stop disabled (parameter No.000E) settings are imported at the system startup. 
Changes while the system is running are invalid. 
2. External forced stop disabled signal (EMID) turns ON at system startup.