CHAPTER 5 ACCESS BETWEEN CPU MODULES AND OTHER MODULES
5
5.2  Acce
ss to Non-
co
ntrolled
 Module
s
5.2.2  L
oadin
g output (
Y
) data
5.2.2
Loading output (Y) data
Data in the output (Y) of output modules and intelligent function modules controlled by other CPU modules can be 
loaded in accordance with the "I/O Sharing When Using Multiple CPUs" setting in PLC parameter ("Multiple CPU 
Setting").
(1) When the "All CPUs Can Read All Outputs" checkbox is checked
The on/off data of output modules and intelligent function modules controlled by other CPU modules can be 
loaded to the output (Y) of the host CPU module.
I/O Sharing When Using Multiple CPUs
     All CPUs Can Read All Outputs:
     Output data can be loaded from the modules 
     controlled by other CPU modules.
     All CPUs Can Read All Outputs:
     Output data cannot be loaded from the modules 
     controlled by other CPU modules.
X0 to XF
Y10 to 
Y1F
X20 to X2F
Y30 to 
Y3F
Input Output Input Output
Point assigned 
to each slot
16
16
16
16
2
2
2
On/off data can be loaded from modules controlled 
by another control CPU.
On/off data can loaded 
by output refresh.
Y30
Slot number
CPU
0
1
2
3
4
Control CPU setting