Справочник Пользователя для Honeywell MRP-2001E

Скачать
Страница из 136
NFPA Standard-Specific Requirements
NFPA 72 Auxiliary Fire Alarm System
120
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
NFPA 72 Remote Station Protective Signaling System
Notes:
1. Cut Jumper JP30 on the MRP-2001/E main circuit board to supervise placement of the 
4XTMF module.
2. Refer to  "4XTMF Transmitter Module Installation" on page 29 for detailed information.
RS82 Remote Station Receiver UL listed.
Refer to Instruction Manual for Remote Station Receiver 
Model RS82.
+        -
Polarity Shown is 
Normal Standby
4XTMF Transmitter Module
Cutting TBL Jumper allows the 
reverse polarity circuit to open 
with a system trouble condition 
if no alarm condition exists.
Power-limited
Figure C.3 Remote Station Connection Using 4XTMF Module
  -
(Dummy load with a 4.7K
Ω, ¼ watt 
resistor when no connection is made)