Installation
Output Circuits
24
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
2.4.2 Special Application DC Power Output Connections
Special Application Resettable and  Nonresettable 24 VDC power is available on the MRP-2001 
control panel.   
2.4.3 Relays - Programmable
The MRP-2001control panel provides a factory default programmed alarm relay, fail-safe trouble 
relay and  supervisory relay.  Each relay can be programmed to activate for other conditions (refer 
to  "On-Board Relays" on page 64).  Each Form-C relay is rated for 2 amps @ 30VDC (resistive) 
and 0.5 amps @ 30 VAC (resistive).
Note that relay connections must be power-limited.
Figure 2.8 Special Application Auxiliary Power
Special Application
4-Wire Smoke Detector Power (500 mA)
 
24 VDC filtered, resettable power for 4-wire smoke detectors 
can be obtained from these terminals (power-limited)
Special Application
Resettable or Nonresettable Power (500 mA)
24 VDC filtered, resettable or nonresettable power can be 
obtained from these terminals (power-limited)
Jumper JP31 pins 1 & 2 for nonresettable power (as 
illustrated in figure to right)
Jumper JP31 pins 2 & 3 for resettable power
-
+
-
+
ms-10UDtb9.cdr
4
3
2
1
Figure 2.9 Relay Terminals
Note:  Relay contacts are shown with 
power applied to the panel and no active 
troubles, alarms or supervisories.
The Trouble Relay is a fail-safe relay 
which will transfer on any trouble or 
total power failure.
m
s10udre
la
y.cdr