Справочник Пользователя для Honeywell MRP-2001

Скачать
Страница из 136
Master Programming Level
Programming
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
71
3.5.7 ANN-BUS
Optional ANN-BUS devices available for the FACP include annunciators, relay modules and 
printer connection for acquiring hardcopy printouts of panel data.  Pressing 1 while viewing 
Programming Screen #3 will cause the control panel to display the following screens.
An ANN-S/PG Printer module, ANN-I/O module, ANN-80 LCD annunciator module, ANN-
RLY relay module and ANN-LED module can be installed in the FACP.  These devices 
communicate with the FACP over the ANN-BUS terminals on the control panel.
3.5.7.1 ANN-BUS Enabled
The ANN-BUS must be enabled if any modules are installed on the ANN-BUS terminals.  To 
enable the ANN-BUS, press 1 while viewing ANN-BUS screen #1 so that the display reads 
ANN-BUS Enabled Yes.  Each press of the 1 key will cause the display to toggle between ANN-
BUS Enabled Yes
 and ANN-BUS Enabled No.
  PROGRAMMING
1=ANN-BUS
2=HISTORY
3=WALKTEST
Programming Screen #3
       ANN-BUS
1=BUS ENABLED      NO
2=BUS MODULES
3=AUTO CONFIGURE
ANN-BUS Screen #1  
       ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-I/O OPTIONS
3=ANN-80 OPTIONS
ANN-BUS Screen #2  
       ANN-BUS
1=ANN-RLY OPTIONS
2=ANN-LED OPTIONS
ANN-BUS Screen #3