Operating Instructions
Read Status
94
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
4.16.3 Output Circuits
Pressing 3 while viewing Read Status Screen #1 will display the following screens:
The operator can press 1 to view the programmed options for Output 1, 2 to view the programmed 
options for Output 2, 3 to view the programmed options for Output 3 or 4 to view the programmed 
options for Output 4.
The resulting screens will display the following information:
Enable/Disable Status
Circuit Type
Silenceable/Nonsilenceable
Auto Silence Enable/Disable and time delay (in minutes)
Silence Inhibit Enabled/Disabled
Coding Selection (Temporal, Steady, etc.)
4.16.4 Cross Input Zones
Pressing 1 while viewing Read Status Screen #2 will display the following screens:
Pressing 1 for Release 1 or 2 for Release 2 will display the cross-zoning, if any, for the selected 
Releasing Circuit as illustrated in the following screen:
The Cross Zone Release screen displays the zones that have been cross-zoned.  In this example, 
Zone 1 is cross-zoned with Zone 4.  
    READ STATUS
1=FACP CONFIG
2=INPUT ZONES
3=OUTPUT CIRCUITS
Read Status Screen #1
    READ OUTPUTS
1=OUTPUT 1
2=OUTPUT 2
3=OUTPUT 3
    READ OUTPUTS
1=OUTPUT 4
Read Outputs Screen #2  
Read Outputs Screen #1  
   READ STATUS
1=CROSS INPUT ZONES
2=ON-BOARD RELAYS
3=SYSTEM SETTINGS
Read Status Screen #2
 CROSS INPUT ZONES
1=RELEASE 1
2=RELEASE 2
Cross Input Zone Screen  
 CROSS ZONE REL 1
       X 1 4   
        NONE
        NONE
Cross Input Zone Screen