9
C
OMPONENT
  D
ESCRIPTION
/
R
EPLACEMENT
_________________
Gas Burner and Ignition System ____
The dryer's gas burner system operates on an “On” or “Off”
gas  rate  sequences  to  accurately  control  the  tumbler’s
(basket's)  drying  temperature.    Maximum  firing  rate  is  2.8
million  Btu/hr.
Upon a call from heat, the dryer computer sends a 120 volt
signal to the burner controller module (BCM) which initiates
and controls the ignition sequences.  The BCM insures that
all  the  safety  switches  are  closed  before  turning  on  the
combustion  air  burner  fan,  then  checks  to  ensure  that  the
burner fan air switch has closed.  The pilot gas flame is then
established,  the  flame  rod,  (which  sits  in  this  pilot  flame),
comes in contact with the flame and signals the BCM.  The
main  motorized  gas  valves  open  in  sequence,  and  full
operational  flame  is  achieved.
The  BCM  has  five  (5)  light  emitting  diodes  (L.E.D.)  on  its
cover and two (2) neon’s on the mounting base for ease of
troubleshooting,  as  well  as  dip  switches  inside  for  ease  of
programming.
!
MAN2374
!
!
Important
Failure  to  comply  with  these  codes  or  ordinances
and/or  the  requirements  stipulated  in  this  manual
can result in personal injury or component failure.
The  dryer  installation  must  meet  the American  National
Standard,  National  Fuel  Gas  Code ANSI  Z223.1-LATEST
EDITION, or in Canada, the Canadian Electrical Codes Parts
1  &  2  CSA  C22.1-1990  or  LATEST  EDITION  (for  Electrical
Connections)  as  well  as,  local  codes  and  ordinances,  and
must be done by a qualified technician.
Note
Undersized gas piping will result in ignition problems
and slow drying and can create a safety hazard.
The dryer must be connected to the type of gas (natural or
liquid propane [L.P.]) indicated on the dryer data label.  If this
information  does  not  agree  with  the  type  of  gas  available,
contact the reseller who sold the dryer or contact the factory.
The gas input ratings shown on the dryer data label are for
elevations up to 2,000 feet (609.6 meters), unless elevation
requirements of over 2,000 feet (609.6 meters) were specified
at the time the dryer order was placed with the factory.  The
adjustment  for  dryers  in  the  field  for  elevations  over  2,000
feet (609.9 meters) is made by changing the burner orifices.
If this adjustment is necessary, contact the reseller who sold
the dryer or contact the factory.
Note
Any  burner  changes  must  be  made  by  a  qualified
technician.
Operational Service Check
Procedure ____________________________
After  performing  any  service  or  maintenance  function,  an
operational  check  should  be  performed  to  ensure  that  all
components  are  performing  properly.
Make  a  complete  operational  check  of  all  the  operating
controls  to  ensure  that  the  timing  is  correct,  temperature
selection  switches  are  functioning  properly.
Make  a  complete  operational  check  of  all  safety  related
circuits, door switches, hi-limit thermostat, sail switch, cycling
thermostats,  etc.
The BCM controls all of the gas burner ignition components,
except for the motorized gas valve.  When the drying set point
temperature is reached, the dryer’s computer closes the top
motorized gas valve, shutting off full flame.
Major  Burner  Components
•
Burner Controller Module (BCM)
The  BCM  provides  effective  burner  flame  safeguard
control  through  adjustable  purge  and  trial-for-ignition
timing.    The  BCM  insures  that  all  dryer  safety  switch
circuits  are  closed,  delays  ignition  to  allow  the
combustion chamber to vent, and insures that a healthy
pilot  flame  is  established  before  opening  the  main  gas
valves.  Five (5) L.E.D.’s on the cover of the BCM allow for
easy  troubleshooting.    Dip  switches  on  the  back  of  the
module  allow  for  easy  programming.
•
Dip  Switches  Selections
Loosen the two (2) screws on the burner control module
cover and pull the module cover off of its base.  The dip
switches are on the back of the cover.
Switch #1 - Recycling Mode
With  this  switch  in  the  “ON”  position,  the  burner  will
recycle  the  ignition  sequence  once  during  each  drying
cycle after a burner fan air switch or main flame failure,
but only if the failure occurs more than 35-seconds after
ignition.  If this switch is “OFF," the burner will lock out at
once.
Switch #2 - Intermittent Pilot
This  switch  is  “ON”  for  intermittent  pilot  or  “OFF”  for
interrupted  pilot.    The  dryer  utilizes  interupted  pilot  so
that the pilot flame doesn’t stay lit during the entire drying
cycle.    With  interrupted  pilot,  the  pilot  flame  goes  out
once  the  main  flame  is  established.
Switch #3 - Trial for Ignition (TFI) Time
When this switch is “ON” a Trial for Ignition (TFI) of ten
(10) seconds is set.  If it is in the “OFF” position, the TFI
is  five  (5)  seconds.    The  Trial  for  Ignition  Time  is  the
length of time that the pilot is given to light.  A ten (10)
second TFI is best for the dryer.
Switch #4, Switch #5, Switch #6, Switch #7- Purge Time
Switch #8 is for post purge selection.  With switch #8 in
the  "ON"  position,  the  post  purge  time  will  be
15-seconds.  When switch #4, switch #5, switch #6, and
switch #7 are in the “OFF” position, the post purge time
will  be  0-seconds.