Справочник Пользователя для Mitsubishi Electronics A8GT-J61BT15

Скачать
Страница из 72
4 - 12                                                                                                                                                       4 - 12
MELSEC-GOT
4   MONITORING SPECIFICATION
4.5  Command List for the Dedicated Command Monitor Method
The command list for the dedicated command monitor is shown below.
Command name
Contents
Reference Section
Initial setting
Initial setting command when monitoring with dedicated
command monitor method (monitoring is performed using
the GOT internal device).
Section 4.6.1
Continuous read
Command to read the specified number of points of data
from the specified head GOT internal device to the remote
register.
Maximum read points
When the number of stations is set to 4 stations: 14 points
When the number of stations is set to 2 stations: 6 points
Section 4.6.2
Random read
Command to read data from several different GOT internal
devices to the remote register.
Maximum read points
When the number of stations is set to 4 stations: 14 points
When the number of stations is set to 2 stations: 6 points
Section 4.6.3
Continuous write
Command to write specified number of points of data from
the remote register to the specified head GOT internal de-
vice.
Maximum write points
When the number of stations is set to 4 stations: 14 points
When the number of stations is set to 2 stations: 6 points
Section 4.6.4
Random write
Command to write remote register data to several different
GOT internal devices.
Maximum write points
When the number of stations is set to 4 stations: 7 points
When the number of stations is set to 2 stations: 3 points
Section 4.6.5
Monitor register
Command to register the GOT internal device number that
performs the always remote register read command.
Maximum registration points
When the number of stations is set to 4 stations: 14 points
When the number of stations is set to 2 stations: 6 points
Section 4.6.6
Monitor request
Command to always read the GOT internal device data
stored by executing the monitor register command to the
remote register.
Section 4.6.7
Always write register
Command to always register the GOT internal device
number of the GOT internal device that performs the always
remote register data write command.
Maximum registration points
When the number of stations is set to 4 stations: 14 points
When the number of stations is set to 2 stations: 6 points
Section 4.6.8
Always write request
Command to always write remote register data to the GOT
internal device registered by executing the always write
register command.
Section 4.6.9