2. DESIGN
 19
2.4.3 Installation
The mounting positions of the main base unit and extension base unit are shown
below.
Connector for SSCNET
40mm (1.57inch)
*1
Main base unit
Extension base unit
30mm
(1.18inch)
min.
70mm
(2.76inch)
min.
Top of enclosure, wiring duct, or other components
Enclosure, etc.
Door
Contactor,
relay, etc.
CPU module
100mm
(3.94 inch)
min.
Fig.2.1 Parallel Installation
*1: If a DIN rail is used, consider the mounting position of the DIN rail.
Duct height 50mm
(1.97inch) max.
30mm
(1.18inch) min.
70mm
(2.76inch) min.
30mm
(1.18
 inch)
min.
*2
Top of enclosure,wiring duct, or other components
Extension base unit
Main base unit
70mm
(2.76inch) min.
*2:Extension Cable Lengths
    A1SC03B cable
    A1SC12B cable
    A1SC30B cable
280mm(11.02inch)max.
1100mm(43.3inch)max.
2900mm(114.17inch)max.
Fig.2.2 Series Installation
Fig.2.3 Clearance to Instruments
            in Front of CPU module
Fig.2.4 Vertical Installation
           (Not Permitted)
Fig.2.5 Horizontal Installation
           (Not Permitted)