Chapter 6    Sequence Program Used for Positioning Control
 
6.5.4 Continuous operation interrupt program 
During positioning control, the control can be interrupted during continuous positioning 
control and continuous path control (continuous operation interrupt function). When 
"continuous operation interruption" is execution, the control will stop when the 
operation of the positioning data being executed ends. To execute continuous 
operation interruption, set "1: Continuous operation interrupt request" for "[Cd.18] 
Interrupt request during continuous operation". 
 
[1]    Operation during continuous operation interruption 
 
Start 
Positioning data No. 10
Positioning data No. 11
Positioning data No. 12
V
t
Stop process when stop command turns ON
Start 
Positioning data No. 10
Positioning data No. 11
Positioning data No. 12
V
t
Stop process at continuous operation 
interrupt request
Cd.18  is set "1"
ON
Stop command
ON
[For Stop command ON]
[For  Cd.18  is set "1" ]
 
 
Fig. 6.12 Operation during continuous operation interruption 
 
 
[2]  Restrictions 
 
(1)  When the "continuous operation interrupt request" is executed, the positioning 
will end. 
Thus, after stopping, the operation cannot be "restarted". 
When "[Cd.6] Restart command" is issued, the warning "Restart not possible" 
(warning code: 104) will occur.