Chapter 16  Troubleshooting
 
16.2 Troubleshooting 
(1)    Troubleshooting using the LEDs 
Check items and corrective actions for troubleshooting using the indicator LEDs 
of the Simple Motion module are described below. 
(a)    When the RUN LED turns off. 
 
Check item 
Action 
Is the power supplied? 
Check that the voltage supplied to the power supply 
module is within the rated range. 
Is the power supply capacity 
sufficient? 
Calculate the total current consumption of the connected 
modules (PLC CPU module, I/O modules, and intelligent 
function modules) and check that the power supply 
capacity is not insufficient. 
Is the module connected correctly? 
Check the state of connection with the module. 
 
If there is no problem on the above check items, a watchdog timer error may 
have occurred. Reset the PLC CPU and check that the RUN LED turns on. 
If not, the possible cause is a hardware failure. Please consult your local 
Mitsubishi representative, explaining a detailed description of the problem. 
 
(b)    When the ERR.LED turns on 
 
Check item 
Action 
Is there a system error? 
An error may have occurred in the PLC CPU. 
Check the error code and take a corrective action. 
 
(c)    When the ERR. LED and axis LED flash 
 
Check item 
Action 
Is there an axis error? 
Check the error code and take the action described in 
Section 16.4. 
 
(d)    When the ERR.LED flashes 
 
Check item 
Action 
Is there a synchronous encoder axis 
error? 
Check the error code and take the action described in 
Section 16.4. 
 
 
(e)    When all LEDs turn on 
Reset the PLC CPU and check that the module is in the normal status. If all 
LEDs still turn on, the possible cause is a hardware failure. Please consult 
your local Mitsubishi representative, explaining a detailed description of the 
problem.