6   MOTION SFC PROGRAMS 
 
6.3 Branch and Coupling Chart List  
Branch and coupling patterns which specify step and transition sequences in the 
Motion SFC charts are shown below.  
 
 
Name  
(Code size (byte))
 
Motion SFC chart symbol 
List 
representation 
Function 
Series transition  
(Corresponding 
symbol size) 
 
 
 
 
List 
representation 
corresponding to 
the Motion SFC 
chart symbols 
shown in Section 
6.2. 
•  Steps and transitions connected in series are 
processed in order from top to bottom.  
•  Steps and transitions need not be lined up 
alternately.  
•  When a transition is omitted, unconditional shift 
processing is performed.  
Selective branch  
((Number of 
branches + 2)  
10)  
 
IFBm
IFT1
IFT2
 
•  The route which transition condition enables first is 
executed after executing the step or transition 
preceding a branch.  
•  Selective branch destinations should always be 
started by transitions, all of which must be Shift or 
WAIT. (Using Shift and WAIT together will cause a 
parallel branch.)  
Selective coupling  
 (8) 
 
IFEm
 
 
 
CALL Kn  
IFBm 
IFT1  
 
SFT Gn  
 
CALL Fn  
 : 
 
 
JMP IFEm  
IFT2  
 
SFT Gn’  
 
CALL Fn’  
 : 
 
 
(JMP IFEm)  
IFEm 
 
CALL Fn’’  
•  After the route branched by a selective branch has 
been processed, execution shifts to a coupling 
point.  
•  A coupling may be preceded and followed by either 
a step or a transition.  
Parallel branch  
(Number of 
branches 22 + 
number of 
coupling 
points 2 + 12)  
 
PABm
PAT1
PAT2
 
•  Multiple routes (steps) connected in parallel are 
executed simultaneously.  
•  Each parallel branch destination may be started by 
either a step or transition.  
Parallel coupling  
                         (8) 
PAEm
 
 CALL 
Kn 
PABm  
PAT1  
 
CALL Fn  
 
SFT Gn’  
 : 
 
 
JMP PAEm  
PAT2  
 
CALL Fn’  
 
SFT Gn’’  
 : 
 
  (JMP PAEm)  
PAEm  
 
CALL Fn’’  
 : 
 
•  Execution waits at the coupling point for executions 
of the routes branched by a parallel branch to be 
completed, and shifts to the next when executions 
of all routes are completed. 
•  A coupling may be preceded and followed by either 
a step or a transition.  
•  When this coupling is preceded by an FS step, 
scans are executed during waiting. After waiting is 
complete, scans are not executed.  
<Normal jump> 
 
 
<Coupling jump>
 
 
CALL Fn 
JMP Pn 
Basic 
type 
Jump transition  
(Corresponding 
symbol size)  
 
 
 
CALL Fn’  
Pn  
 CALL 
Kn 
 
1) Normal jump  
•  After the step or transition preceding this jump 
transition is executed, execution shifts to the 
pointer Pn specified within its own program.  
•  The jump destination may either be a step or 
transition.  
•  When a jump takes place from an FS step to a 
transition, scans are executed during waiting for 
the completion of  transition condition of the 
jump destination.  
2) Coupling jump  
•  When a jump to the other route within a parallel 
branch takes place after the parallel branch, a 
"coupling jump" takes place and execution waits 
at the jump destination.