19   ERROR CODE LISTS 
 
19.3 Motion SFC Parameter Errors 
Motion SFC parameters are checked by SW6RN-GSV P. 
 
Table 19.6 PLC ready flag (M2000) OFF   ON errors (17000 to 17009) 
Error factor 
Error code 
Name Description 
Error Processing 
Corrective Action 
17000 
Normal task 
consecutive 
transition count 
error 
• The normal task's consecutive transition count 
of the Motion SFC program started by the 
normal task is outside the range 1 to 30. 
The initial value of 3 is 
used for control. 
17001 
Event task 
consecutive 
transition count error 
• The set number of consecutive transitions of 
the Motion SFC program started by the event 
task is outside the range 1 to 10. 
17002 
NMI task 
consecutive 
transition count error 
• The set number of consecutive transitions of 
the Motion SFC program started by the NMI 
task is outside the range 1 to 10. 
The initial value of 1 is 
used for control. 
Turn PLC ready flag (M2000) OFF, make 
correction to set the value within the range, 
and write it to the CPU. 
 
Table 19.7 SFC Program start errors (17010 to 17019) 
Error factor 
Error code 
Name Description 
Error Processing 
Corrective Action 
17010 
Executed task 
setting is illegal 
• Among the normal, event and NMI tasks, more 
than one or none of them has been set. 
17011 
Executed task 
setting is illegal 
(event) 
• Two or more fixed cycles of the event task have 
been set. 
The initial value (normal 
task) is used for control. 
Turn PLC ready flag (M2000) OFF, make 
correction, and write a correct value to the 
CPU.