5 - 52 
Chapter 5    Data Used for Positioning Control
 
[Pr.95]
 
External command signal selection 
QD77MS16
 
 
Set the external command signal. 
0: Not used ........ External command signal is not used. 
1: DI1 ................. DI1 is used as external command signal. 
2: DI2 ................. DI2 is used as external command signal. 
3: DI3 ................. DI3 is used as external command signal. 
4: DI4 ................. DI4 is used as external command signal. 
 
Note) The "External command signal selection" is included in detailed parameters 
2, but it will be valid at the rising edge (OFF to ON) of the PLC READY 
signal [Y0]. 
 
 
POINT 
 
Same external command signal can be used in the multiple axes. 
 
 
 
 
5.2.5 OPR basic parameters 
Item 
Setting value, setting range 
Default 
value 
Buffer memory address 
Value set with GX Works2 
Value set with sequence 
program 
QD77MS2 
QD77MS4 
QD77MS16
[Pr.43] 
OPR method 
0 : Near-point dog method 
0 70+150n 
4 : Count method 1) 
5 : Count method 2) 
6 : Data set method   
7 : Scale origin signal detection 
method 
[Pr.44]
 
OPR direction 
0 : Positive direction (address 
increment direction) 
0 71+150n 
1 : Negative direction (address 
decrement direction) 
[Pr.45]
 
OP address 
The setting value range differs depending on the "[Pr.1] Unit 
setting". 
72+150n 
73+150n 
[Pr.46]
 
OPR speed 
74+150n 
75+150n 
[Pr.47]
 
Creep speed 
76+150n 
77+150n 
[Pr.48]
 
OPR retry 
0 : Do not retry OPR with limit 
switch 
0 78+150n 
1 : Retry OPR with limit switch
 
n: Axis No.-1