Chapter 5    Data Used for Positioning Control
 
5.7.3 Expansion axis control data 
Setting item 
Setting details 
 
 
 
 
[Cd.180] Axis stop 
QD77MS16
 
 When the axis stop signal turns ON, the OPR control, positioning control, JOG 
operation, inching operation, manual pulse generator operation, speed-torque 
control, etc. will stop. 
 By turning the axis stop signal ON during positioning operation, the positioning 
operation will be "stopped". 
 Whether to decelerate stop or suddenly stop can be selected with "[Pr.39] Stop 
group 3 sudden stop selection". 
 During interpolation control of the positioning operation, if the axis stop signal of 
any axis turns ON, all axes in the interpolation control will decelerate and stop. 
 
Fetch cycle: Operation cycle 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
[Cd.181] Forward run JOG start 
QD77MS16
 
 When the JOG start signal is ON, JOG operation will be carried out at the "[Cd.17] 
JOG speed". When the JOG start signal turns OFF, the operation will decelerate 
and stop. 
 When inching movement amount is set, the designated movement amount is 
output for one operation cycle and then the operation stops. 
 
Fetch cycle: Operation cycle 
 
 
 
 
 
[Cd.182] Reverse run JOG start 
QD77MS16
 
 
 
 
 
 
[Cd.183] Execution prohibition flag 
QD77MS16
 
 If the execution prohibition flag is ON when the positioning start signal turns ON, 
positioning control does not start until the execution prohibition flag turns OFF. 
Used with the "Pre-reading start function". (Refer to Section 13.7.7) 
 
Fetch cycle: At start