Chapter 6    Sequence Program Used for Positioning Control
 
6.5 Program details 
6.5.1 Initialization program 
[1]    OPR request OFF program 
This program forcibly turns OFF the "OPR request flag" ([Md.31] Status: b3) 
which is ON. 
When using a system that does not require OPR, assemble the program to 
cancel the "OPR request" made by the Simple Motion module when the power is 
turned ON, etc. 
 
  Data requiring setting 
 
Set the following data to use the OPR request flag OFF request. 
 
Setting item 
Setting 
value 
Setting details 
Buffer memory address
QD77MS2 
QD77MS4 
QD77MS16
[Cd.19] 
OPR request flag OFF 
request 
Set to "1: Turn OPR request flag OFF". 
1521+100n  4321+100n
 
n: Axis No.-1 
:
 Refer to Section 5.7 "List of control data" for details on the setting details. 
 
  Time chart for OPR OFF request 
 
OFF
ON
OFF
0
1
0
ON
OFF
PLC READY signal
 [Y0]
READY signal 
[X0]
OPR request OFF flag
( Md. 31 Status: b3)
Cd. 19 OPR request flag OFF request
 
 
Fig. 6.1 Time chart for OPR OFF request 
 
[2]    External command function valid setting program 
This program is used to validate the "external command signal" beforehand when 
using the external command functions (external start, speed change, speed-
position switching, position-speed switching, skip). Set which function to use 
beforehand in "[Pr.42] External command function selection". 
(Set the external command signal (DI) in "[Pr.95] External command signal 
selection" at QD77MS16 use.) 
Set the following data to validate the "external command signal". 
 
Setting item 
Setting 
value 
Setting details 
Buffer memory address
QD77MS2 
QD77MS4 
QD77MS16
[Cd.8]  External command valid 
Set to "1: Validate external command". 
1505+100n  4305+100n
 
n: Axis No.-1 
:
 Refer to Section 5.7 "List of control data" for details on the setting details.