Chapter 6    Sequence Program Used for Positioning Control
 
6.5.6 Stop program 
The axis stop signal or stop signal from external input signal is used to stop the control. 
Create a program to turn ON the axis stop signal as the stop program. 
 
Signal 
QD77MS2 
QD77MS4 
QD77MS16 
Axis stop signal 
Y4, Y5 
Y4, Y5, Y6, Y7 
[Cd.180] Axis stop 
 
Each control is stopped in the following cases. 
 
(1)    When each control is completed normally 
(2)    When the Servo READY signal is turned OFF 
(3)    When a PLC CPU error occurs 
(4)    When the PLC READY signal is turned OFF 
(5)    When an error occurs in Simple Motion module 
(6)    When control is intentionally stopped 
(Stop signal from PLC CPU turned ON, "Stop signal" of external input signal 
turned ON, etc.) 
 
The stop process for the above cases is shown below. 
(Excluding "(1) When each control is completed normally" above.) 
 
[1] Stop 
process 
 
Stop cause 
Stop 
axis 
M code 
ON signal 
after stop 
Axis operation 
status after 
stopping 
([Md.26]) 
Stop process 
OPR control 
Major 
positioning 
control 
High-level 
positioning 
control 
Manual control 
Machine 
OPR control
Fast OPR 
control 
JOG/ 
Inching 
operation 
Manual pulse 
generator 
operation 
Forced stop 
"Forced stop input 
signal" OFF from an 
external device 
All 
axes 
No change Servo OFF 
Servo OFF or free run (The operation stops with dynamic 
brake) 
 
Servo READY OFF 
  • Servo amplifier 
power supply OFF Each 
axis 
No change
Servo amplifier 
has not been 
connected 
  • Servo alarm 
Error 
  • Forced stop input 
to servo amplifier 
Servo OFF 
Fatal stop   
(Stop group 1) 
Hardware stroke limit 
upper/lower limit 
error occurrence 
Each 
axis 
No change Error 
Deceleration stop/sudden stop   
(Select with "[Pr.37] Stop group 1 sudden stop selection".) 
Deceleration 
stop 
Emergency stop   
(Stop group 2) 
Error occurs in PLC 
CPU 
All 
axes 
No change
Error 
Delegation stop/sudden stop   
(Select with "[Pr.38] Stop group 2 sudden stop selection".) 
Deceleration 
stop 
PLC READY signal 
OFF 
Turns OFF
Error in test mode 
No change
Relatively safe stop 
(Stop group 3) 
Axis error detection 
(Error other than stop 
group 1 or 2) 
Each 
axis 
No change Error 
Deceleration stop/sudden stop   
(Select with "[Pr.39] Stop group 3 sudden stop selection".) 
Deceleration 
stop 
"Stop" input from GX 
Works2 
Intentional stop 
(Stop group 3) 
"Axis stop signal" ON 
from PLC CPU 
Each 
axis 
No change
Stopped 
(Standby) 
"Stop signal" of 
external input signal 
ON