Справочник Пользователя для Bosch ICP-CC404

Скачать
Страница из 98
ICP-CC404 | Installation Guide | 11.0   Dialer Information 
 
 
Bosch Security Systems, Inc. | 12/08 | F01U089401-02 
47
 
 
When Receivers 1 or 2 is set up for 
domestic reporting, telephone numbers 
programmed into these locations are 
ignored. Refer to Section 6.1.2 
Changing Domestic Phone Numbers
 on 
page 28 (using the Installer Code 
function) or Section 6.2.3 Changing 
Domestic Phone Numbers
 on page 33 
(using the Master Code Function). 
 
11.2  Secondary Telephone Number for 
Receiver 1 and Receiver 2 
Program the Secondary Telephone Number for 
Receiver 1 in 
Locations 016 to 031.  
Program the Primary Telephone Number for 
Receiver 2 in 
Locations 056 to 071. 
The default value for both telephone numbers is  
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0. 
Refer to Section 11.1 Primary Telephone Number for 
Receiver 1 and Receiver 2
 on page 46 for programming 
information. 
 
 
When Receivers 1 or 2 are set up for 
domestic reporting, telephone numbers 
programmed into these locations are 
ignored. Refer to Section 6.1.2 
Changing Domestic Phone Numbers
 on 
page 28 (using the Installer Code 
function) or Section 6.2.3 Changing 
Domestic Phone Numbers
 on page 33 
(using the Master Code Function). 
 
11.3  Handshake Tone for Receiver 1 and 
Receiver 2 
Program the Handshake Tone for Receiver 1 in 
Location 032.  
Program the Handshake Tone for Receiver 2 in 
Location 072.  
The default value for both Handshake Tones is 
1. 
These locations set the type of handshake tone 
required for the receivers before data transmissions to 
the monitoring station begin. The options are: 
1 – HI LO Handshake 
HI LO Handshake Tone is required to communicate 
in Contact ID Format or High Speed DTMF. 
2 – 1400 Hz 
1400 Hz Handshake Tone is required to 
communicate in Ademco Lo Speed Format or 
Domestic Dialing Format. 
3 – 2300 Hz 
Reserved. 
4 – No Handshake 
Setting these locations to No Handshake Tone is not 
recommended. 
5 – Pager 
Pager Handshake Tone is required to communicate in 
Basic Pager Format. 
11.4  Transmission Format for Receiver 1 
and Receiver 2 
Program the Transmission Format for Receiver 1 in 
Location 033.  
Program the Transmission Format for Receiver 2 in 
Location 073.  
The default value for both Transmission Formats is 
1. 
These locations select the data format used to send 
reports to the base station receiver. These locations 
also allow you to configure the control panel for 
domestic or basic pager formats. The options are: 
1 – Contact ID 
2 – 4 + 2 express 
3 – FSK 300 baud Bell 
4 – Domestic 
5 – Basic Pager 
7 – Reserved 
 
The Basic Pager option supports only 
eight zones due to protocol limitations. If 
you use more than eight zones, this 
option is not recommended. 
If you use the Zone 16, the 4+2 Express 
and FSK 300 Baud formats are not 
recommended because Zone 16 will be 
assigned as "0" and some receivers will 
not support this zone. 
 
11.5  Subscriber ID Number for Receiver 
1 and Receiver 2 
Program the Subscriber ID Number for Receiver 1 in 
Locations 034 to 039.  
Program the Subscriber ID Number for Receiver 2 in 
Locations 074 to 079. 
The default value for both Subscriber ID Numbers is 
0 0 0 0 0 0. 
The Subscriber ID Number is sent to identify the 
calling control panel.  
For Basic Pager Format, Locations 034 to 036 (for 
Receiver 1) and Locations 074 to 076 (for Receiver 2) 
are ignored and the first digit of the Subscriber ID 
Number must start in Location 037 (Receiver 1) and 
Location 077 (Receiver 2).