ICP-CC404 | Installation Guide | 12.0   Dialer Options 
 
 
50 Bosch 
Security 
Systems, 
Inc. | 12/08 | F01U089401-02
 
The options are: 
1 – Display FAULT Indicator When the Telephone 
Line Fails 
When this options is selected, the FAULT indicator 
flashes and the codepad buzzer beeps once per 
minute if the control panel detects that the telephone 
line is disconnected. Refer to Section 4.13 Fault 
Descriptions
 on page 22 for more information. 
2 – Sound Alarm When System Is Armed 
To use Option 2, you must also select Option 1. If the 
control panel detects that the telephone line is 
disconnected when the system is armed, the horn 
speaker, bell, and strobe outputs are activated.  
4 – Sound Alarm when System Is Disarmed 
You must also select Option 1 to use this option. If 
the control panel detects that the telephone line is 
disconnected when the system is disarmed, the horn 
speaker, bell, and strobe outputs are activated.  
 
 
If you program 7 in this location, the horn 
speaker, bell, strobe, and EDMSAT 
outputs are all activated when the system 
is armed or disarmed. 
 
8 – Reserved 
 
12.0  Dialer Options 
When programming these locations, there are up to 
four options per location. You can select any 
combination of the options by programming a single 
value. Calculate this value by adding the option bit 
numbers together. Refer to Section 2.3 Programming 
Option Bits
 on page 10 for more information. 
12.1  Dialer Options 1 
Program the selected Dialer Options 1 in 
Location 
177.  
The default value is
 9. 
The options are: 
1 – Dialer Reporting Functions Allowed 
If you select this option, the dialer operates for all 
functions. 
If you do not select this option, the communication 
dialer does not operate.  
Upload/Download using the CC816 Alarm Link 
Software and telephone remote arming remain 
operational regardless of this setting. 
2 – Remote Arming by Telephone Allowed 
If you select this option, you can remotely arm the 
system using a standard telephone with the CC911 
Phone Controller or by pressing [*] on your touch-
tone telephone. Refer to Section 7.0 Remote Arming by 
Telephone
 on page 38 for more information. Forced 
arming is automatically assumed when this feature is 
used. Refer to Section 14.3.6 Zone Options 2 on page 58 
for more information on forced arming. 
Remote arming by telephone is not affected by 
whether remote functions are enabled or disabled. 
Refer to Section 11.10 Ring Count on page 49 for 
programming the number of rings before the control 
panel answers an incoming call. 
4 – Answering Machine Bypass Only When Armed 
Select this option to enable the Answering Machine 
Bypass feature when the system is armed. When the 
system is disarmed, the control panel does not answer 
any incoming calls. This option is useful in high 
telephone traffic installations where the control panel 
could answer an incoming call. Refer to Section 11.10 
Ring Count
 on page 49 to program Answering 
Machine Bypass. 
8 – Use Bell 103 for FSK Format (Disabled = CCITT 
V21) 
If this option is selected, the control panel uses the 
BELL 103 transmission frequency at 300 baud. If this 
option is not selected, the control panel uses the 
CCITT V21 transmission frequency at 300 baud. 
12.2  Dialer Options 2 
Program the selected Dialer Options 2 in 
Location 
178.  
The default value is
 0. 
The options are: 
1 – Open/Close Reports Only if Previous Alarm 
When selected, an Opening Report is sent to the base 
station receiver when the system is disarmed after an 
alarm occurred. When the system is armed, a Closing 
Report is sent. An Opening or Closing Report is not 
sent again until the system registers another alarm. 
Open/Close Reports must be enabled in Locations 
333 and 334 (refer to Section 15.6 Open/Close Reports on 
page 61) for this option to work. 
 
If the system is disarmed when an alarm 
occurs, only a Closing Report is sent the 
next time the system is armed. 
 
2 – Open/Close Reports for STAY Mode 1 and 
STAY Mode 2 
Select this option if Open and Close Reports are 
required when the system is armed in STAY Mode 1 
or STAY Mode 2.