SECTION 8: C
ONTROL
 M
ETHODS
  
27
Buildings today demand all sorts of control options 
based on the user’s preference. ULTRAVAC™ 
controls offer a host of communication options for 
integration with controls’ networks to best serve 
individual needs:
BACnet
®
: Interface ULTRAVAC™ with other building 
management control platforms with our BACnet 
option.
TCP/IP (LAN): Connect to ULTRAVAC™ via your 
local area network of computers. Load ULTRAVAC™ 
software onto any computer on the network and 
control and view your heating system from your 
computer.
MODEM: Dial into ULTRAVAC™ from anywhere in 
the world via modem. Supplied as standard on all 
central controllers!
RS-485: Hard wire ULTRAVAC™ directly to your 
computer.
There are references in this manual  to various trademarks. All 
trademarks mentioned herein, whether registered or not, are the 
property of their respective owners. Roberts-Gordon is not 
sponsored by or affiliated with any of the trademark or registered 
trademark owners, and make no representations about them, 
their owners, their products or services. 
Roberts-Gordon LLC is not sponsored by or affiliated with 
BACnet®.
8.3 SPST Transformer Relay (P/N 90417600K)
The transformer relay can be used to control an EP-
100 or EP-201 pump CORAYVAC
®
 system. The single 
pole relay can only be used to control one zone of 
burners. The electrical circuit is a 120 V AC (20 A) 
supply. The transformer 24 V AC output for the ther-
mostat is rated at 40 V A. Thermostats used with the 
transformer must not exceed this power requirement. 
A transformer relay operated system will not give any 
post purge pump operation to completely exhaust 
products of combustion from the system or provide 
indication of operating conditions. The transformer 
relay wiring diagram is shown in the CORAYVAC
®
 
Installation, Operation and Service Manual (P/N 
127102NA). 
8.4 DPST Transformer Relay (P/N 90436300)
The transformer relay can be used to control an EP-
100 or EP-201 pump CORAYVAC
®
 system. The double 
pole relay can only be used to control two zones of 
burners. The electrical circuit is a 120 V AC (20A) sup-
ply. The transformer 24 V AC output for the thermostat 
is rated at 40 VA. Thermostats used with the trans-
former must not exceed this power requirement. A 
transformer relay operated system will not give any 
post purge pump operation to completely exhaust 
products of combustion from the system or provide 
indication of operating conditions. The transformer 
relay wiring diagram is shown in the CORAYVAC
®
 
Installation, Operation and Service Manual (P/N 
127102NA).
8.5 Pressure Switch
A pressure switch is required to confirm pump opera-
tion on all systems. 
A pressure switch is also required on the inlet duct of a 
non-pressurized air supply.