SECTION 13: TROUBLESHOOTING
13.1 General
Ensure proper air flow 
clearance for axial fan. 
Open louvers slightly.
Replace axial fan if it does 
not operate.
If problems persist, contact
Roberts-Gordon LLC at
www.rg-inc.com
Heater Operating
TROUBLESHOOT ENDS.
No
Replace limit switch.
The limit switch has 
tripped. See Manual Reset 
Limit Switch Figure.
No
Use Troubleshooting for
Automatic Ignition Burner
Systems section to test burner.
Has burner “Locked Out”?
Yes
No
With external controls (i.e. 
thermostat) on, does the 
burner continue through the 
heating cycle?
No
Yes
Does the flue 
blower run?
No
Use Troubleshooting for 
Flue Blower section to test 
fan.
Yes
Yes
Burner has locked out due 
to ignition failure. Use 
Troubleshooting for 
Automatic Ignition Burner 
Systems section to test 
burner.
Is ignition control showing a 
"2 flashes" LED code?
Yes
No
Yes
Fan and limit switch are 
operating normally.
Replace temperature
limit switch.
No
Turn on supplies.
START
UHA 30 - 75: Press in reset 
button on manual reset limit 
switch. UHA 100 - 125: Wait 
10 - 15 minutes for limit 
switch to cool. Does fan 
stop running?
No
Yes
Is ignition control showing a 
"4 flashes" LED code
?
Yes
Are gas & electrical
supplies on?
No 
Yes
No
WARNING
Explosion Hazard
Installation, service and annual inspection 
must be done by a contractor qualified in 
the installation and service of gas-fired 
heating equipment or your gas supplier.
Turn off gas and electrical supplies before 
performing service or maintenance.
Failure to follow these instructions can 
result in death, injury or property damage.