Canadian installations, all electrical connections must be made in
accordance with Canadian Electrical Code CSA C22.1, or authori-
ties having jurisdiction.
NOTE:
Proper polarity must be maintained for 115-v wiring. If
polarity is incorrect, control status code indicator light will flash
rapidly and furnace will not operate.
The cabinet MUST have an uninterrupted or unbroken ground
according to NEC ANSI/NFPA 70-1999 and Canadian Elec-
trical Code CSA C22.1 or local codes to minimize personal
injury if an electrical fault should occur. This may consist of
electrical wire or conduit approved for electrical ground when
installed in accordance with existing electrical codes. Do not
use gas piping as an electrical ground. Failure to follow this
warning could result in electrical shock, fire, or death.
24-V WIRING
Make field 24-v connections at the 24-v terminal strip. (See Fig.
14.) Connect terminal Y as shown in Fig. 15 for proper operation
in cooling mode. Use AWG No. 18 color-coded wire only.
The 24-v circuit contains an automotive-type, 3-amp fuse located
on the main control board. Any direct shorts during installation,
service, or maintenance could cause this fuse to blow. If fuse
replacement is required, use ONLY a 3-amp fuse of identical size.
ACCESSORIES
1. Electronic Air Cleaner (EAC)
Two spring clamp terminals (for 12 gage maximum, solid or
stranded wire), marked EAC-1 and EAC-2, are provided for
EAC connection. (See Fig. 14.) These terminals are energized
with 115v (1.5-amp maximum) during blower motor opera-
tion. To connect EAC power leads to furnace control board,
strip approximately 1/8 in. of insulation from wire. Open
terminal by depressing switch arm with a screwdriver or
finger, and insert wire as shown in Fig. 16.
2. Humidifier (HUM)
Screw terminals (HUM and C
OM
-24V) are provided for 24-v
humidifier connection. The terminals are energized with 24v
(0.5-amp maximum) after inducer motor prepurge period.
Do not connect furnace control HUM terminal to HUM
(humidifier) terminal on Thermidistat™, Zone Controller, or
similar device. See Thermidistat, Zone Controller, thermostat,
or controller manufacturer’s instructions for proper connec-
tion. A failure to follow this warning could result in fire.
NOTE:
A field-supplied, 115-v controlled relay connected to
EAC terminals may be added if humidifier operation is desired
during blower operation.
Step 11—Venting
Refer to the national or local installation code such as NFGC in the
United States, or the NSCNGPIC in Canada for proper vent sizing
and installation requirements. Use the enclosed Installation In-
structions (Single-Stage Vent Tables for Category I Fan-Assisted
Furnaces) for a quick, easy reference.
After fully assembling the vent connector to the furnace flue collar,
securely fasten the vent connector to the collar with two field-
supplied, corrosion-resistant, sheet metal screws located 180° apart
and midway up the collar.
The horizontal portion of the venting system shall maintain a
minimum of 1/4-in. upward slope per linear ft and it shall be
rigidly supported every 5 ft or less with hangers or straps to ensure
that there will be no movement after installation.
Table 6—Electrical Data
UNIT SIZE
VOLTS—
HERTZ—
PHASE
OPERATING VOLTAGE RANGE
MAXIMUM
UNIT AMPS
MINIMUM
WIRE GAGE
MAXIMUM WIRE
LENGTH FT‡
MAXIMUM
FUSE OR CKT BKR
AMPS†
Maximum*
Minimum*
050-08
115—60—1
127
104
6.6
14
42
15
050-12
115—60—1
127
104
8.1
14
34
15
070-08
115—60—1
127
104
6.7
14
42
15
070-12
115—60—1
127
104
8.4
14
33
15
096-12
115—60—1
127
104
9.2
14
30
15
096-16
115—60—1
127
104
10.2
14
28
15
115-16
115—60—1
127
104
10.1
14
28
15
115-20
115—60—1
127
104
13.3
12
33
20
115-22
115—60—1
127
104
15.2
12
29
20
135-20
115—60—1
127
104
14.3
12
31
20
* Permissible limits of the voltage range at which the unit will operate satisfactorily.
† Time-delay type is recommended.
‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
Fig. 13—Typical Gas Pipe Arrangement
A89414
GAS
SUPPLY
MANUAL
SHUTOFF
VALVE
(REQUIRED)
SEDIMENT
TRAP
UNION