2.  Make sure jumper setting for input type is set for thermocouple TC-PT, middle jumper. 
3.  Return controller to housing. 
4.  Press the Display button for one (1) second to enter Menu Display. 
5.  Press the Up Arrow button to get to Setup mode. 
6.  To switch parameters within Setup mode, press the Display button. 
Figure 8: 
Setting List for Process Temperature Controller, Part No. A0548565 
Mode Parameter 
Setting 
range  Default 
Factory 
setting 
Protect  SECr Security  
0 to 6 
Protect  YEYP A/M Key Protect  ON/OFF 
OFF 
ON 
Manual  Manual MV 
-5.0 to 105.0% 
0.0 
Default 
 
Mode Parameter 
Setting 
range  Default 
Factory 
setting 
Level 0  SP Set Point 
SP Lower Limit to Upper Limit EU 
Default 
Level 0  r-S Run/Stop 
Run/Stop  
Run 
Default 
Level 1  SP-0 Set Point 0  
SP Lower to Upper EU 
Default 
Level 1  SP-1 Set Point 1  
SP Lower to Upper EU 
Default 
Level 1  AL-1 Alarm Value 1 
-1999 to 9999 EU  
25.0 
Level 1  AL-2 Alarm Value 2 
-1999 to 9999 EU 
25.0 
Level 1  AL-3 Alarm Value 3 
-1999 to 9999 EU  
Default 
Level 1  P Proportional Band  
0.1 to 999.9% FS 
10.0 
4.4 
Level 1  I Integral Time  
0 to 3999 SEC 
233 
84 
Level 1  d Derivative Timer 
0 to 3999 SEC 
40 
13 
Level 1  C-SC Cooling 
Coefficient  
0.01 to 99.99 
1.00 
Default 
Level 1  C-db Dead Band  
-19.99 to 99.99%FS 
0.00 
Default 
Level 1  6F-r Manual Reset 
Value 
0.0 to 100.0% 
50.0 
Default 
Level 1  HYS Hysteresis (Heat)  0.01 to 99.99%FS 
0.10 
Default 
Level 1  CHYS Hysteresis (Cool)  0.01 to 99.99%FS 
0.10 
Default 
Level 1  CP Control Period 
(Heat) 
1 to 99 SEC 
20 
Default 
Level 1  C-CP Control Period 
(Cool) 
1 to 99 SEC 
20 
Default 
 
Mode Parameter 
Setting 
range  Default 
Factory 
setting 
Level 0  SP Set Point 
SP Lower Limit to Upper Limit EU 
Default 
Level 0  r-S Run/Stop 
Run/Stop  
Run 
Default 
Level 1  SP-0 Set Point 0  
SP Lower to Upper EU 
Default 
Level 1  SP-1 Set Point 1  
SP Lower to Upper EU 
Default 
Level 1  AL-1 Alarm Value 1 
-1999 to 9999 EU  
25.0