 System Description
 
 
 
The Manning GM-1 is designed to accept a single 
4/20 mA current input signal, plus provide a regulated  
24 VDC supply to operate all sensors manufactured by 
Honeywell Analytics. 
 
 
 
The Manning GM-1 is housed in a rugged 14 gauge 
gasketed steel enclosure. Behind the clear plexiglass 
window is a 20-segment vertical LED bargraph display 
which gives a visual indication of the gas 
concentration. 
 
 
 
 
The unit has warning and alarm level indications on the 
front panel, and warning and alarm relays allowing the 
user to incorporate functions such as ventilation 
control, remote horns, security system monitoring, and 
automatic shutdown. 
 
 
 
Designed to be highly reliable when properly installed, 
all relays are energized during normal operation, and a 
sensor fault monitoring circuit will indicate a fault and 
trip a dedicated fault relay if the signal falls below  
1.4 mA. 
 
 
 
 
The unit has an audible horn which will sound if an 
alarm or fault condition is detected. The silence switch 
will silence the horn until the next event. If an alarm 
condition initiates the horn, the horn will clear 
automatically when the alarm relay clears. 
 
 
 
 
The unit has a power-up delay feature that places all 
outputs in normal conditions for one minute to allow for 
sensor stabilization. 
 
 
The Manning GM-1 will support all of Manning 
sensors, including oxygen, which requires a down-
scale alarm. 
 
 
All components that are in contact with voltages above  
40 volts are UL listed, including the enclosure. 
 
 
Note:  The Manning GM-1 is for use in 
non-classified areas only. 