ARCHITECTURAL AND ENGINEERING SPEC 
INSTALLATION OF ALARM
The explosive gas/CO combination  alarm shall be a First Alert Model GCO1 and shall 
provide at a minimum the following features and functions:
1. An electrochemical CO sensor and a metal oxide explosive gas sensor.
2. The unit shall have a digital display with peak CO memory feature
3. The unit shall be capable of self restoring and provide an end of life timer.
4. 120V AC powered with a 9V alkaline battery backup and a solid state piezo horn
rated at 85dB at 10 ft.
5. A visual green LED power-on indicator to confirm unit is receiving power. A visual 
red indicator to show unit is alarm.
6. A full function test button should check all alarm functions by simulating an 
explosive gas and CO condition, causing the unit to alarm.
  7. Two Silence features - Low Battery Silence: Silence low battery chirp for up to 8 
hours. Alarm Silence: Temporarily silence unwanted nuisance alarms.
8. An infrared remote (IR) feature to test and/or silence the alarm with most 
standard IR remote controls.
9. The unit shall be capable of operating between 40°F (4°C) and
100°F (38°C) and relative humidity between 10% and 95%.
10. The unit shall contain mounting hardware and shall be listed for wall
mounting.
11. The unit shall at a minimum meet the requirements of UL1484, UL2034, NFPA 
720, ICC.
Installation of this alarm must conform to NFPA 720. Always check your local building 
codes. Follow all instructions for placement as outlined in the user’s manual.
SHIPPING SPECS:
TECHNICAL SPECS
Individual Carton Dimensions 
5.813 ”L x 2.938”W x 3.438”H
   Weight 
0.69lbs.
   Cube 
0.034 ft3
   UPC 
0 29054 00045 3
Master Carton Dimensions 
9.125”L x 7.125”W x 6.313”H
Master Pack
  Weight 
4.35lbs.
   Cube 
0.238 ft3
   UPC 
600 29054 00045 5
Pallet Information 
   Cases per Layer
27 
   Number of Layers
7
   Cases per Pallet 
189
   Units per Pallet 
1,134
   Cube
55.2 ft3
   Weight
887 lbs.
©2009 BRK Brands, Inc. a Jarden Corporation 
Company (NYSE: JAH)
3901 Liberty Street Road
Aurora, IL  60504-8122
All rights reserved
First Alert is a registered trademark of the First Alert Trust
BRK is a registered trademark of BRK Brands, Inc.
CM2914
THE PARTS OF THIS GAS/CO ALARM
1.  Test/Silence button &     
            remote control sensor
2.  Power Light (GREEN)
3.  Display
4. Alarm Horn (behind cover)
5. Display Button: Press to 
recall highest CO level 
recorded.
6. 9V Battery compartment
3.1"
TOP VIEW
SIDE VIEW
BACK VIEW
2.5"
 
 
 
Alarm Dimensions: 
3.1”H x 5.7"L x 2.5"D
Weight: 
9.6 oz.
Operating Voltage: 
120V AC with 9V Alkaline Battery Backup
Temperature Range: 
40F (4C) to 100F (38C)
Humidity Range:
10% to 95% relative humidity (RH)
Audio Alarm:
85dB at 10 feet
Test/Silence:
Electronically simulates both explosive gas and CO 
conditions, causing the unit to alarm or temporarily 
silence the alarm         
   Remote:
Use vol/chn buttons on most household IR remotes.
   Manual:
Press and hold test/silence button
Alarm Reset:
Automatic when explosive gas and/or CO clears
CO Sensor:
Electrochemical
Gas Sensor:
Thick film metal oxide
Indicator Lights/Sounds:
   AC Power:
Constant green light
   DC Power:
Intermittent green Light
   Gas Alarm:
Audio Alarm (continuous beeps), rapidly flashing red light 
   CO Alarm:
Audio Alarm (4 beeps, pause, 4 beeps), rapidly 
flashing red light
   Digital Display:
Displays hazard (Gas or CO), battery level or CO levels in 
parts per million (PPM)
Listing:
ETL to UL1484 and 2034 Standards
CAT. 
GCO1B
CO
5.7"
2
3
4
1
5
6