COMBUSTIBLE WALLS (Fig. 25):  Cut a 9-3/8"H x 9-3/8"W (240
mm x 240 mm) hole through the exterior wall and frame as shown
(Fig. 24).
NON-COMBUSTIBLE WALLS (Fig. 25):  Hole opening must be
7.5" (190 mm) in diameter.
(240mm)
9-
3/8
"
 9-
3/8
"
(240mm)
 7-
1/2
"
(190mm)
Vent Opening — 
Combustible Wall
Vent Opening — 
Noncombustible Wall
(framing detail)
Fig. 25
  STEP 1
Locate vent opening on the wall.  It may be necessary to first
position the fireplace and measure to obtain hole location.
Depending on whether the wall is combustible or non-
combustible, cut opening to size. Fig. 25.
(For combustible walls first frame in opening).
VERTICAL SIDEWALL INSTALLATION
VERTICAL SIDEWALL APPLICATION
  STEP 2
Fig. 26.  Measure wall thickness and cut adjustable zero
clearance sleeve parts to proper length (MAXIMUM 12"/
305mm).  Adjust sleeve to minimum (9-3/8" x 9-3/8") and
attach to firestop with #8 sheet metal screws (supplied).
Install firestop assembly.
Zero clearance sleeve is only required for
combustible walls.
Fig. 26
     #8
SCREWS(2)
ADJUSTABLE ZERO 
CLEARANCE SLEEVE
       
ADJUSTABLE 
ZERO CLEARANCE
SLEEVE
     #8
SCREWS(2)
     #8
SCREWS(2)
Maximum Length 
12" (294mm)
FIRESTOP
WOOD FRAMING 
WALL EXTERIOR 
 
VENT PIPE 
 
FIRESTOP
ZERO
CLEARANCE
SLEEVE
FLUSH WITH
WALL
EXTERIOR
DRYWALL