c.  caulking  or  sealants  are  applied  to 
areas  such  as  joints  around  window 
and door frames, between sole plates 
and floors, between wall-ceiling joints, 
between  wall  panels,  at  penetrations 
for plumbing, electrical, and gas lines, 
and at other openings. 
If your home meets all of the three criteria 
above, you must provide additional fresh air. 
See Ventilation Air From Outdoors
, page 8. 
If your home does not meet all of the three 
criteria  above,  proceed  to  Determining 
Fresh-Air Flow For Fireplace Location
.
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1.3/ 
NFPA 54
 defines a confined space as a space 
whose volume is less than 50 cubic feet per 
1,000 Btu per hour (4.8 m
3
 per kw) of the ag-
gregate input rating of all appliances installed 
in that space and an unconfined space as a 
space whose volume is not less than 50 cubic 
feet per 1,000 Btu per hour (4.8 m
3
 per kw) 
of the aggregate input rating of all appliances 
installed in that space. Rooms communicating 
directly with the space in which the appliances 
are installed*, through openings not furnished 
with doors, are considered a part of the un-
confined space.
* Adjoining rooms are communicating only if 
there are doorless passageways or ventilation 
grills between them.
aIR FoR CoMBUsTIon and VenTIlaTIon
Continued
DETERMINING FRESH-AIR FLOW 
FOR FIREPLACE LOCATION
Determining if You Have a Confined or 
Unconfined Space
Use this work sheet to determine if you have 
a confined or unconfined space.
Space: Includes the room in which you will install 
fireplace  plus  any  adjoining  rooms  with  door-
less passageways or ventilation grills between 
the rooms.
1.  Determine the volume of the space (length 
x width x height).
 
Length x Width x Height =__________cu. ft. 
(volume of space)
 
Example: Space size 20 ft. (length) x 16 ft. 
(width) x 8 ft. (ceiling height) = 2560 cu. ft. 
(volume of space)
 
If  additional  ventilation  to  adjoining  room 
is supplied with grills or openings, add the 
volume of these rooms to the total volume 
of the space. 
  30,000
  26,000
  56,000
2.  Multiply the space volume by 20 to determine 
the maximum Btu/Hr the space can support.
 
  ________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
 
Example: 2560 cu. ft. (volume of space) x 20 
=  51,200  (maximum  Btu/Hr  the  space  can 
support)
3.  Add the Btu/Hr of all fuel burning appliances 
in the space.
 
Vent-free fireplace 
 __________ Btu/Hr
 
Gas water heater* 
 __________ Btu/Hr
 
Gas furnace 
 __________ Btu/Hr
 
Vented gas heater 
 __________ Btu/Hr
 
Gas fireplace logs 
 __________ Btu/Hr
 
Other gas appliances* + _________ Btu/Hr
 
Total 
= _________ Btu/Hr
 
* Do not include direct-vent gas appliances. 
Direct-vent  draws  combustion  air  from  the 
outdoors and vents to the outdoors.
 
Example: 
 
Gas water heater 
 __________ Btu/Hr
 
Vent-free fireplace 
+ _________ Btu/Hr
 
Total 
= _________ Btu/Hr
4.  Compare the maximum Btu/Hr the space 
can support with the actual amount of Btu/
Hr used.
 
  _______ Btu/Hr  (maximum  the  space  can 
support) 
 
  _______ Btu/Hr  (actual  amount  of  Btu/Hr 
used)
 
Example:  51,200  Btu/Hr  (maximum  the 
space can support) 
 
 
56,000 Btu/Hr (actual amount of 
Btu/Hr used)
The space in the above example is a confined 
space because the actual Btu/Hr used is more 
than  the  maximum  Btu/Hr  the  space  can  sup-
port. You must provide additional fresh air. Your 
options are as follows:
A.  Rework worksheet, adding the space of an 
adjoining room. If the extra space provides an 
unconfined space, remove door to adjoining 
room or add ventilation grills between rooms. 
See  Ventilation  Air  From  Inside  Building, 
page 8.
B.  Vent  room  directly  to  the  outdoors.  See 
Ventilation Air From Outdoors, page 8.
C.  Install a lower Btu/Hr fireplace, if lower Btu/Hr 
size makes room unconfined. 
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support, the space is 
an unconfined space. You will need no additional 
fresh air ventilation.