CDVSC7 & CDV7 Series Gas Fireplace
4
69D3011
VenTInG InSTallaTIon     
Below GRaDe InSTallaTIon
When it is not possible to meet the required vent terminal 
clearances  of  1”  (305  mm)  above  grade  level,  a  snor-
kel kit is recommended. It allows installation depth down 
to  7”  (178  mm)  below  grade  level.  The  7”  (178  mm)  is 
measured from the center of the horizontal vent pipe as it 
penetrates through the wall.
ensure the sidewall venting clearances are observed. 
If venting system is installed below ground, we rec-
ommend  a  window  well  with  adequate  and  proper 
drainage to be installed around the termination area.
If installing a snorkel, a minimum 4” (610 mm) vertical 
rise is necessary. The maximum horizontal  run with the 
4”  vertical  pipe  is  36”  (914  mm). This  measurement  is 
taken from the collar of the fireplace (or transition elbow) 
to the face of the exterior wall. See the Sidewall Venting 
Graph for extended horizontal run if the vertical exceeds 
4” (610 mm).
1.  Establish  vent  hole  through  the  wall.  Page  22,  Figure 
26
.  Remove soil to a depth of approximately 16” (406 mm) 
below base of snorkel. Install drain pipe. Install window 
well  (not  supplied).  Refill  hole  with  1”  (305  mm)  of 
coarse  gravel  leaving  a  clearance  of  approximately  4” 
(10 mm) below snorkel. Figure 31
3.  Install vent system.
4.  Ensure a watertight seal is made around the vent pipe 
coming through the wall.
5.  Apply  high  temperature  sealant  caulking  (supplied) 
around the 4” and 7” snorkel collars.
6.  Slide the snorkel into the vent pipes and secure to the 
wall.
7.  Level the soil so as to maintain a 4” (10 mm) clearance 
below snorkel. Figure 31
BG402a
Top Vent
Below grade installation
1/26/00   djt
Firestop
7” Pipe
7TDVSNORK 
(Snorkel)
4” (10 mm) 
Clearance 
Min.
Window 
Well
Gravel
Drain
BG40a
Figure 31 - 
Below Grade Installation
*A minimum of 4” (610 mm) verti-
cal  pipe  must  be  installed  when 
using the 7TDVSNORK Kit.
4” (610 mm) 
Minimum*
Screws
Foundation Wall
Do not back fill around snorkel.
a clearance of at least 4” must be maintained 
between the snorkel and the soil.
If  the  foundation  is  recessed,  use  recess  brackets  (not 
supplied) for securing lower portion of the snorkel. Fasten 
brackets to wall first, then secure to snorkel with self drill-
ing #8 x 1/ sheet metal screws. It will be necessary to 
extend vent pipes out as far as the protruding wall face. 
Figure 32
BG401
Snorkel
2/10/99   djt
Snorkel
Wall Screws
Foundation 
Recess
Watertight 
Seal Around 
PIpe
Sheet Metal Screws
BG401
Figure 32 - 
Snorkel installation, recessed foundation
VeRTICal ThRouGh-The-RooF applICa-
TIon
his gas fireplace has been approved for:
  Vertical installations up to 40’ (1 m) in height. Up to 
a 10’ (3 m) horizontal vent run can be installed within 
the vent system using a maximum of two 90° elbows. 
Figure 33
  Up to two 45° elbows may be used within the horizontal 
run. For each 45° elbow used on the horizontal plane, 
the  maximum  horizontal  length  must  be  reduced  by 
18” (450 mm). 
example: Maximum horizontal length:
 
No elbows 
=  10’ (3 m)
 
1 x 45° elbow  =  8.5’ (.6 m)
 
 x 45° elbows  =  7’ (.1 m)
  A minimum of an 8’ (.5 m) vertical rise is required.
  Two sets of 45° elbow offsets may be used within the 
vertical sections. From 0 to a maximum of 8’ (.5 m) of 
vent pipe can be used between elbows. Figure 33
  7DVCS  supports  offsets.  Figure  37.  This  application 
will require that you first determine the roof pitch and 
use the appropriate starter kit. (Refer to Venting Com-
ponents List)
  The maximum angular variation allowed in the system 
is 70°. Figure 34