41
TROUBLESHOOTING 
STANDING PILOT IGNITION
SYMPTOM POSSIBLE 
CAUSE 
ACTION
4.  Frequent pilot outage 
problem. 
5.  The pilot and main 
burner extinguish 
while in operation 
6. Glass 
Soots 
7.  Flame burn blue and 
lifts off burner (ghost-
ing)
A.  Pilot flame may be too high or 
too low, causing pilot safety 
to drop out 
A.  Inner vent pipe leaking 
exhaust gases back into 
system 
B.  Horizontal vent improperly 
pitched 
C.  Improper vent cap installation
A. Flame impingement on logs 
A. Insufficient oxygen being 
supplied 
A.  Clean and adjust the pilot flame for maximum flame impinge-
ment on thermocouple.
A.  Check for flue product leak. Replace defective pipe section.
B.  Check horizontal-venting piping is running upward 1/4" per foot. 
Do not run the pipe level or downward. 
C. Check for proper installation and freedom from debris or block-
age.
A. Install log set per the instructions  
  Inspect the injector and air intake area. Make sure this area does 
not have any blockage from debris and clean.  
  Check gas supply.
A. Ensure that the vent cap is installed properly and free of debris. 
Ensure that the vent system joints are tight and have no leaks.  
Ensure that no debris has been blocking the inner air intake at the 
bottom back of the combustion chamber.  Ensure that the glass is 
properly secure and latch.