Справочник Пользователя для Lopi Freedom Fireplace Insert
Installation
(for qualified installers only)
9
© Travis Industries
100-01162
4041105
Insert Placement Requirements
•
The insert must be placed so that no combustibles are within, or can swing within (e.g. drapes,
doors), 36" of the front of the insert
doors), 36" of the front of the insert
•
Insert and hearth must be installed on a level, secure floor
•
The minimum clearances, facing, and hearth requirements in Figure 3 must be met.
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
Side
Wall
Wall
Combustible Mantel
Combustible Top Facing
Non-Combustible
Hearth
Facing
Extended
(stock)
Minimum Clearances
k
l
m
n
o
p
q
x
Sidewall to Insert
Side Facing
Top Facing
with mantel shield
Mantel to Insert
with mantel shield
Hearth (Front)
Hearth (Side)
Front of Insert
Extension onto Hearth
15"
13-1/2"
30"
17"
32"
19"
16"
8"
36"
7"
q
l
k
p
x
o
n
m
With
Flush Kit
15"
13-1/2"
20"
N/A
20"
N/A
16"
8"
36"
1-5/8"
Figure 3
Hearth Requirements
•
Must extend 16" in front of the insert and 8" on both sides
•
Must be non-combustible and at least .018" thick (26 gauge)
Masonry Fireplace Requirements
•
Chimney must have a clay tile liner or a stainless steel liner (positive connection)
•
Entire fireplace, including chimney, must be clean and undamaged. Any damage must be repaired
prior to installation of the insert
prior to installation of the insert
•
Chimney height: 15' minimum; 33' maximum.
•
Entire fireplace, including chimney, must meet local building requirements