Installation 
(for qualified installers only)
9
© Travis Industries
100-01162
4041105
Insert Placement Requirements
 
The insert must be placed so that no combustibles are within, or can swing within (e.g. drapes,
doors), 36" of the front of the insert
 
Insert and hearth must be installed on a level, secure floor
 
The minimum clearances, facing, and hearth requirements in Figure 3 must be met.
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
AAAAAAAAAAAAAA
Side 
Wall
Combustible Mantel
Combustible Top Facing
Non-Combustible 
Hearth
Facing
Extended
(stock)
Minimum Clearances
k
l
m
n
o
p
q
x
Sidewall to Insert
Side Facing
Top Facing
 with mantel shield
Mantel to Insert
 with mantel shield
Hearth (Front)
Hearth (Side)
Front of Insert
Extension onto Hearth
15"
13-1/2"
30"
17"
32"
19"
16"
8"
36"
7"
q
l
k
p
x
o
n
m
With 
Flush Kit
15"
13-1/2"
20"
N/A
20"
N/A
16"
8"
36"
1-5/8"
Figure 3
Hearth Requirements
 
Must extend 16" in front of the insert and 8" on both sides
 
Must be non-combustible and at least .018" thick (26 gauge)
Masonry Fireplace Requirements
 
Chimney must have a clay tile liner or a stainless steel liner (positive connection)
 
Entire fireplace, including chimney, must be clean and undamaged.  Any damage must be repaired
prior to installation of the insert
 
Chimney height: 15' minimum; 33' maximum.
 
Entire fireplace, including chimney, must meet local building requirements