360DVS Series Direct Vent Fireplaces
10006326
Fig. 14  Termination clearances.
General Information Assembling Vent Pipes
Canadian Installations:
Venting system must be installed in accordance with the 
current CSA-B149.1 installation code.
USA Installations:
The venting system must conform with local codes and/
or current National Fuel Gas Code ANSI Z223.1/NFPA 
54.
Only venting components manufactured by CFM Corpo-
ration can be used in Direct Vent systems. 
Twist Lock Pipes
When using twist-lock pipe, it is not necessary to use 
sealant on the joints. The only areas of the venting 
system that need to be sealed with high-temperature 
silicone sealant are the sliding joints of telescopic vent 
sections used in the system.
To join the twist lock pipes together, align the beads 
of the male end with the grooves of the female end. 
While bringing the pipes together, twist the pipe until the 
flange on the female end contacts the external flange 
on the male end. It is recommended that you secure the 
joints with three (3) sheet metal screws; however, this is 
not mandatory with twist lock pipe.
NOTE:  For ease of assembly, use a lubricant (Vaseline 
or similar substance) on male end of twist lock pipe 
prior to assembly. 
Male End
Female End
Screw Holes
TWL100
Fig. 15  Twist lock pipe joints.
Outside Corner
Inside Corner
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors. 
G =
Combustible 
  6" (152 mm)
Noncombustible 
  2" (51 mm)
F =
Combustible 
  6" (152 mm)
 
Noncombustible 
  2" (51 mm)
G
Balcony - 
with no side wall
M = 
Combustible &
Noncombustible
  12" (305 mm)
M
Balcony - 
with perpendicular side wall
M = 24" (610 mm)
P = 20” (508 mm)
M
F
Alcove Applications*
C
D
C
E
V
V
Combustible &
Noncombustible
V
V
V
E
 = Min. 6” (152 mm) for 
non-vinyl sidewalls
Min. 12” (305 mm) for
vinyl sidewalls
O
 = 8’ (2.4 m) Min.
O
P
584-15
 
No. 
  of Caps 
 
D
Min.
 
  C
Max.
 
3’ (914 mm)  2 x D
Actual
 
6’ (1.8 m) 
1 x D
Actual
 
9’ (2.7 m) 
2/3 x D
Actual
 
12’ (3.7 m)  1/2 x D
Actual
D
Min.
 = # of Termination caps x 3
C
Max.
 = (2 / # termination caps) x D
Actual
*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions 
specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All 
mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All 
gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.