 P48-2 Zero Clearance Direct Vent Gas Fireplace
8
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest 
importance that this fi replace and vent system be installed only in accordance with these instructions.
Clearance to Combustibles from:
Back 0" 
(0mm) 
Side 0" 
(0mm) 
Floor 0" 
(0mm)
Minimum Clearance from Top of Front Facing:
Mantel min. 
8" 
(203mm)
Ceiling 
39" 
(990mm) from top of front facing 
  
 
above 
louvers.
Side Wall:
  
6" 
(152mm)
Horizontal Vent Clearances:
Top 
2-1/2" (64mm)
Side 
1-1/2" (38mm)
Bottom 
1-1/2" (38mm)
Vertical  Vent  Clearances:
  
1-1/4"  (32mm) 
 
Alcove Clearances:
Max. Depth 36" 
(914mm)
Min. Width 60" 
(1524mm)
Min. Height 80" 
(2032mm)
INSTALLATION
The  HeatWave Duct Kit 
and the Heat Release Kit 
have different clearance 
and framin requirements, 
check the HeatWave and 
Heat Release manual for 
details.
Heat Release Kit
Caution Requirements
The top,  back and sides of the fi replace are defi ned by 
standoffs. The metal ends of the standoff may NOT be 
recessed into combustible construction.
WARNING
Fire hazard is an extreme risk 
if these clearances (air space) to combustible materials 
are not adhered to. It is of greatest importance that this 
fi replace and vent system be installed only in
accordance with these instructions.