CB1200-I Pellet Insert
G. Calculating Alternate Floor Protection Material
 
Thermal Conductivity: k value
The k value indicates the amount of heat (in BTU’s) that will flow 
in 1 hour through 1 square foot of a uniform material 1 inch thick 
for each degree (F) of temperature difference from one side of 
the material to the other.  The LOWER the k factor means less 
heat is being conducted through the non-combustible material to 
the combustible material beneath it.  The k value of a material 
must be equal or smaller then the required k value to be accept-
able.
 
 
(BTU) (inch)
 
 
(foot
2
 (hour) (
o
F)
Thermal Resistance: R value
The R value is a measure of a material’s resistance to heat 
transfer.  R value is convenient when more than one materi-
al is used since you can add the R values together, whereas 
you can not do this for k value.  The HIGHER the R factor 
means less heat is being conducted through the non-com-
bustible material to the combustible material beneath it.  The 
R value of a material must be equal or larger then the re-
quired R value to be acceptable.
Converting k to R:
Divide 1 by k and multiply the results times the thickness in inch-
es of the material.
 
R = 1/k x inches of thickness
Converting R to k:
Divide the inches of thickness by R.
 
k = inches of thickness/R
Calculations:
Example: Floor protection requires k value of 0.84 and 3/4 inch 
thick.
Alternative material has a k value of 0.6 and is 3/4 inch thick.
Divide 0.6 by .75 = k value of 0.80.  This k value is smaller than 
0.84 and therefore is acceptable.
H.  Prefabricated Metal Chimney
The chimney can be new or existing, masonry or prefabricated 
and must meet the following minimum requirements:
  • Must  be  minimum  6  inch  (152mm)  inside  diameter  of 
high temperature chimney listed to UL 103 HT (2100
o
F) 
or ULC-S628.
  • Must use components required by the manufacturer for 
installation.
  • Must maintain clearances required by the manufacturer 
for installation.
  • Refer to manufacturers instructions for installation
  •This insert is listed to UL 1482 Standard and is approved 
for installation into listed factory-built zero clearance fire-
places listed to UL 127 conforming to the following speci-
fications and instructions:
  •The  original  factory-built  clearance  fireplace  chimney 
cap  must  be  re-installed  after  installing  the  approved 
chimney  liner  meeting  type  UL  103  HT  requirements 
(2100°F) per UL 1777.
  •If the chimney is not listed as meeting HT requirements, 
or if the factory built fireplace was tested prior to 1998, a 
full height listed chimney liner must be installed from the 
appliance flue collar to the chimney top.
  •The liner must be securely attached to the insert flue collar 
and the chimney top. 
  •The air flow of the factory-built zero-clearance fireplace 
system must not be altered. The flue liner top support 
attachment must not reduce the air flow for the existing 
air-cooled chimney system.
  •No dilution air is allowed to enter the chimney.
    1. Secure the fireplace damper in the open position.  If 
this cannot be accomplished, it will be necessary to 
remove the damper 
 
    2. Seal  damper  area  of  chimney  around  chimney 
connector with a high temperature sealant or seal 
insert against the face of the fireplace.
    3. Both methods must be removable and replaceable 
for cleaning and re-installation.