6
Mobile Home
1.  An outside air inlet must be provided for the combustion 
air and must remain clear of leaves, debris, ice and/or 
snow.  It must be unrestricted while the appliance is 
in  use  to  prevent  room  air  starvation  which  causes 
smoke spillage.  Smoke spillage can also set off smoke 
alarms.  
2.  The combustion air duct system must be made of metal.  
It must permit zero clearance to combustible construc-
tion and prevent material from dropping into the inlet or 
into the area beneath the dwelling and contain a rodent 
screen.
3.  The appliance must be secured to the mobile home 
structure by bolting it to the floor (using lag bolts) in two 
places.  Use the same holes that secured the appliance 
to the shipping pallet.
4.  The appliance must be grounded with #8 solid copper 
grounding wire or equivalent, terminated at each end 
with an NEC approved grounding device.
5.  Refer to Clearances to Combustibles and floor pro-
tection requirements on pages 9 & 10 for listings to 
combustibles and appropriate chimney systems.
6.  Use  silicone  to  create  an  effective  vapor  barrier  at 
the location where the chimney or other component 
penetrates to the the exterior of the structure.
7.  Follow the chimney manufacturer’s instructions when 
installing the vent system for use in a mobile home.
8.  Installation shall be in accordance with the Manufactur-
ers Home & Safety Standard (HUD) CFR 3280, Part 
24.
Installation must comply with Manufactured Home and 
Safety Standard (HUD), CFR 3280, Part 24.
WARNING
You must use a Quadra-Fire Outside Air Kit 
for installation in a mobile home.
A. Mobile Home Installation
Spark Arrestor Cap
Roof Flashing
Storm Collar
Joist Shield/Firestop
Approved Class “L” 
or “PL” Pellet Vent
Figure 17.1
CAUTION
Never draw outside combustion air from:
•  Wall, floor or ceiling cavity
•  Enclosed space such as an attic or garage
CAUTION
THE STRUCTURAL INTEGRITY OF THE MOBILE HOME 
FLOOR, WALL AND CEILING/ROOF MUST BE MAIN-
TAINED
Do NOT cut through:
•  Floor joist, wall, studs or ceiling trusses.
•  Any supporting material that would affect the structural 
integrity.
NEVER INSTALL IN A SLEEPING ROOM.
Consumes oxygen in the room.
WARNING
Asphyxiation Risk.