VENT TERMINAL CLEARANCES 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
A= Clearance above grade, verandah, porch, deck, or 
balcony [*12 inches (30 cm) minimum] 
 
5
B= Clearance to window or door that may be opened  
[*12 inches (30 cm) minimum] 
C= Clearance to permanently closed window        
[minimum 12 inches (30 cm) recommended to prevent 
condensation on window] 
D= Vertical clearance to ventilated soffit located above the 
terminal within a horizontal distance of 2 feet (60 cm) 
from the center-line of the terminal (24 inches (60 cm) 
minimum) 
E= Clearance to unventilated soffit 
[18 inches (45 cm) minimum] 
F= Clearance to outside corner [12 inches minimum] 
G= Clearance to inside corner [`12 inches minimum] 
H= *Not to be installed above a meter/regulator assembly 
within 3 feet (90 cm) horizontally from the center-line of 
the regulator 
I= Clearance to service regulator vent outlet  
[*6 feet (1.8m) minimum] 
J= Clearance to non-mechanical air supply inlet to building 
or the combustion air inlet to any other appliance  
[12 inches (30 cm) minimum] 
K= Clearance to a mechanical air supply inlet  
[*6 feet (1.8m) minimum] 
L=*** Clearance above paved side-walk or paved driveway 
located on public property  
[*7 feet (2.1m) minimum] 
M= Clearance under verandah, porch, deck, or balcony 
[*24 inches (60 cm) minimum **] 
 
*** A vent shall not terminate directly above a sidewalk or paved driveway, which is located between two single family dwellings 
and serves both dwelling  
**  Only permitted if verandah. Porch, deck, or balcony is fully open on a minimum of 2 sides beneath the floor 
As specified in CGA B149 Installation Codes (1991) Note: Local Codes or Regulation 
 
WHEN VENTING THIS APPLIANCE YOU MUST STAY WITHIN THE 
SHADED AREA (see venting chart provided) FOR ALL VENTING 
APPLICATIONS. 
Installations over 15 feet 
(4.5m) vertical require the 
use of a vent restrictor 
 
VENT RESTRICTOR RING:
 A vent restrictor ring is supplied with each 
direct vent fireplace. This restrictor ring is to be installed when the vertical 
chimney installation is over 15’ (4.57 M). Before the chimney is placed onto 
the stove, place this vent restrictor ring into the 4” (10.16 CM) flue pipe(as 
shown), once the vent restrictor ring has been installed, the vertical sections 
of chimney can 
be installed.