Table 1 — 50VQP Unit Physical Data
           LEGEND
NOTES:
1. All units have grommet and spring compressor mountings, and
2.2 cm and 3.5 cm electrical knockouts.
2. Use the lowest maximum pressure rating when multiple options
are combined:
UNIT 50VQP
084
096
120
150
168
192
240
300
COMPRESSOR QUANTITY
Scroll (1)
Scroll (2)
   Factory Charge HFC-410A (kg) per circuit
3.97
4.42
6.35
7.03
3.97
4.42
6.35
7.03
BLOWER MOTOR
   Blower Motor Quantity
1
   Standard Motor (kW)
.75
1.12
1.49
2.24
1.49
2.24
3.73
3.73
   Large Motor (kW)
1.12
1.49
2.24
3.73
2.24
3.73
5.60
5.60
BLOWER
   No. of Blowers
1
2
   Blower Wheel Size D x W (cm)
38.1 x 27.9
38.1 x 
38.1
38.1 x 27.9
38.1 x 
38.1
WATER CONNECTION SIZE
   FPT (in.) [mm]
1-1/2 [38.1]
2 [50.8]
2-1/2 
[63.5]
COAX VOLUME
   Volume (liters)
8.28
9.37
13.11
18.29
24.08
27.98
CONDENSATE CONNECTION SIZE
   FPT (in.) [mm] 
1 [25.4]
AIR COIL DATA
   Air Coil Dimensions H x W (cm)
91.4 x 121.9
91.4 x 121.9
   Air Coil Total Face Area (sq m) 
1.11
2.22
   Air Coil Tube Size (cm)
3/8 [0.953]
   Air Coil Fin Spacing (fins per cm)
5.5
4.72
5.5
4.72
   Air Coil Number of Rows
2
3
4
2
3
4
MISCELLANEOUS DATA
   Filter Standard Throwaway (qty) (cm)
(4) 45.74 x 63.5 x 2.5
(8) 45.74 x 63.5 x 2.5
   Weight - Operating (kg)
399
422
435
725
755
769
   Weight - Packaged (kg)
406
429
442
739
769
782
FPT — Female Pipe Thread
OPTION
MAXIMUM PRESSURE (kPa)
Base Unit
3100
Motorized Water Valve
2750
Internal Secondary Pump
  999
T
Optional Discharge
Supply Air
Optional Discharge
Access
Panel
Access
Panel
Access
Panel
Access
Panel
Vibration
Pad
Control Box
Supply Air
Supply Water
Return
Water
Balancing
Valve
Valves
Trap
Condensate
24 V Remote
Mtd. Stat
Power
Supply
Disconnect
Switch or
Per Local Codes
Condensate
Water In
Water Out
Unions
Fig. 1 — Typical 50VQP Unit Installation