Справочник Пользователя для Carrier GT-S

Скачать
Страница из 56
Indoor & Outdoor Split 
Geothermal Comfort Systems
Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05
17
 CFM = airfl ow, cubic feet/minute
 EWT = entering 
water 
temperature, 
˚F
 GPM = water 
fl ow in US gallons/minute
  EAT  =  entering air temperature, Fahrenheit 
  
 
(dry 
bulb/wet 
bulb)
 HC 
air 
heating 
capacity, 
Mbtuh
 
TC  =  total cooling capacity, Mbtuh
 
SC  =  sensible cooling capacity, Mbtuh
 
KW  =  total power unit input, KiloWatts
 
HR  =  total heat of rejection, Mbtuh
 
HE  =  total heat of extraction, Mbtuh
  HWC  =  Hot Water Generator (desuperheater)    
  
 
capacity, 
Mbtuh
   WPD  =  Water coil pressure drop (psi & ft hd)
 EER = Energy 
Effi ciency Ratio
 
   
= BTU output/Watt input
 COP = Coeffi cient of Performance
 
   
= BTU output/BTU input
 LWT = leaving 
water 
temperature, 
°F
 
LAT  =  leaving air temperature, °F
 
LC  =  latent cooling capacity, Mbtuh
 
S/T  =  sensible to total cooling ratio
LWT = EWT -
HE
GPM x 500
LAT = EAT +
HC
CFM x1.08
LWT = EWT +
HR
GPM x 500
LAT (DB) = EAT (DB)  -
SC
CFM x1.08
LC = TC - SC
S/T =
SC
TC
Heating
Cooling
Heating Corrections
Cooling Corrections
Sens Clg Cap Multiplier - Entering DB 
°F
Ent Air DB
°F
Htg Cap
Power
Heat of
Ext
Ent Air
WB 
°F
Total Clg
Cap
70
75
80
80.6
85
90
95
Power
Heat of
Rej
60
1.019
0.896
1.054
60
0.881
0.943
1.067
1.192
1.240
*
*
*
0.983
0.899
65
1.010
0.948
1.028
65
0.940
0.797
0.952
1.106
1.125
1.261
*
*
0.991
0.949
68
1.004
0.980
1.011
66.2
0.976
0.693
0.868
1.043
1.063
1.217
*
*
0.997
0.980
70
1.000
1.000
1.000
67
1.000
0.624
0.812
1.000
1.023
1.188
1.343
1.352
1.000
1.000
75
0.997
1.059
0.979
70
1.012
0.697
0.820
0.835
0.944
1.067
1.257
1.002
1.010
80
0.993
1.118
0.957
75
1.024
0.637
0.658
0.817
0.983
1.159
1.005
1.019
Rev. 5/2/00M
*
 Sensible capacity equals total capacity (no latent capacity) at conditions shown as "
*
"
ARI/ISO/ASHRAE 13256-1 uses entering air conditions of Clg- 80.6
°F DB/66.2°F WB and Htg- 68°F DB/59°F WB
GT-GS & GT-S Performance Correction Factors