Справочник Пользователя для Carrier 50XT

Скачать
Страница из 38
3
MODEL NUMBER NOMENCLATURE
50XT
0
1
024
3
Type of Unit
50XT -  Packaged
            Electric Heat Pump
Nominal Cooling Capacity
024
 - 2 Ton
030 - 2.5 Ton
036 - 3 Ton
042 - 3.5 Ton
048 - 4 Ton
060 - 5 Ton
N/A
– – –
Options
BT -  AL evap, vinyl condens
CC -  AL evap, CU condens
CU -  CU evap & condens
TP -  Base unit with tin plated 
         indoor coil hairpins
TV -  TP with vinyl coating on outdoor coil
TC -  TP with AL indoor coil and 
         CU/CU outdoor coil
Only used if ordering an option
– –
Series
Electrical Supply
3- 208/230-1-60
Packaging
LEGEND
AL - Aluminum
CU - Copper
ARI* CAPACITIES
Cooling Capacities and Efficiencies
UNIT
50XT
NOMINAL
TONS
STANDARD CFM (High/Low Stage)
(Cooling & Heating)
NET COOLING CAPACITIES (Btuh)
(High/Low Stage)
EER @A{
SEER‡
024
2
800 / 600
22,600 / 17,600
11.4
15.5
030
2--1/2
1000 / 700
28,600 / 21,400
11.6
15.0
036
3
1200 / 850
34,600 / 24,400
12
15.0
042
3--1/2
1500 / 975
40,500 / 29,000
11.6
15.0
048
4
1600 / 1100
46,000 / 33,400
11
15.0
060
5
1750 / 1200
57,000 / 40,500
11
14.5
Heating Capacities and Efficiencies
UNIT
50XT
HIGH HEAT CAPACITY
(BTUH) @ 47°F (8.3°C)
(High/Low Stage)
HIGH HEAT COP
@ 47°F (8.3°C)
(High/Low Stage)
LOW HEAT CAPACITY
(BTUH) @ 17°F (--8.3°C)
(High/Low Stage)
LOW HEAT COP
@ 17°F (--8.3°C)
(High/Low Stage)
HSPF‡
024
20,800 / 16,800
3.3 / 3.2
11,600 / 8,400
2.2 / 1.8
8.0
030
27,600 / 20,400
3.5 / 3.5
14,000 / 9,600
2.1 / 1.9
8.0
036
33,600 / 23,000
3.4 / 3.4
17,200 / 11,200
2.4 / 1.7
8.0
042
39,500 / 27,600
3.6 / 3.5
20,600 / 14,200
2.3 / 2.0
8.0
048
45,500 / 32,200
3.3 / 3.5
25,000 / 15,200
2.4 / 1.9
8.0
060
56,000 / 39,500
3.2 / 3.3
30,800 / 20,400
2.2 / 1.9
8.0
{
”A” conditions---80°F (26.6°C) indoor db/67°F (19.4°C) indoor wb & 95°F (35°C) outdoor db.
}
Rated in accordance with U.S. Government DOE (Department of Energy) test procedures and/or ARI Standards 210/240.
** Tested in accordance with ARI Standard 270---95 (not listed in ARI).
NOTES:
1. Ratings are net values, reflecting the effects of circulating fan heat. Ratings are based on:
Cooling Standard: 80°F (26.6°C) db, 67°F (19.4°C) wb indoor entering ---air temperature and 95°F (35°C) db outdoor entering---air temperature.
2. Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.
LEGEND
dBA—Sound Levels (decibels)
db—Dry Bulb
SEER—Seasonal Energy Efficiency Ratio
wb—Wet Bulb
COP—Coefficient of Performance
HSPF—Heating Season Performance Factor
50X
T