Справочник Пользователя для Carrier RVR

Скачать
Страница из 44
41
Table 30 — Troubleshooting
LEGEND
RV — Reversing Valve
FAULT
HEATING COOLING
POSSIBLE CAUSE
SOLUTION
Main Power Problems
X
X
Green Status LED Off
Check line voltage circuit breaker and disconnect.
Check for line voltage between L1 and L2 on the contactor.
Check for 24 vac between R and C on controller.
Check primary/secondary voltage on transformer.
HP Fault — Code 2
High Pressure
X
Reduced or no water flow in 
cooling
Check pump operation or valve operation/setting.
Check water flow adjust to proper flow rate.
X
Water temperature out of 
range in cooling
Bring water temperature within design parameters.
X
Reduced or no airflow in 
heating
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
Dirty air coil — construction dust etc.
External static too high. Check Tables 8-13.
X
Air temperature out of range 
in heating
Bring return air temperature within design parameters.
X
X
Overcharged with refrigerant Check superheat/subcooling vs typical operating condition Table 21.
X
X
Bad HP switch
Check switch continuity and operation. Replace.
LP/LOC Fault — Code 3
Low Pressure/Loss of 
Charge
X
X
Insufficient charge
Check for refrigerant leaks.
X
Compressor pump down at 
start-up
Check charge and start-up water flow.
FP1 Fault — Code 4
Water Freeze Protection
X
Reduced or no water flow in 
heating
Check pump operation or water valve operation/setting.
Plugged strainer or filter. Clean or replace.
Check water flow adjust to proper flow rate.
X
Inadequate antifreeze level
Check antifreeze density with hydrometer.
X
Improper freeze protect set-
ting (30
 F vs 10 F)
Clip JW2 jumper for antifreeze (10
 F) use.
X
Water temperature out of 
range
Bring water temperature within design parameters.
X
X
Bad thermistor
Check temperature and impedance correlation.
FP2 Fault — Code 5
Air Coil Freeze
Protection
X
Reduced or no airflow in 
cooling
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
External static too high. Check Tables 8-13.
X
Air temperature out of range Too much cold vent air. Bring entering air temperature within design
parameters.
X
Improper freeze protect set-
ting (30
 F vs 10 F)
Normal airside applications will require 30 F only.
X
X
Bad thermistor
Check temperature and impedance correlation.
Condensate Fault —
Code 6
X
X
Blocked drain
Check for blockage and clean drain.
X
X
Improper trap
Check trap dimensions and location ahead of vent.
X
Poor drainage
Check for piping slope away from unit.
Check slope of unit toward outlet.
Poor venting. Check vent location.
X
Moisture on sensor
Check for moisture shorting to air coil.
Over/Under Voltage —
Code 7
(Auto Resetting)
X
X
Under voltage
Check power supply and 24 vac voltage before and during operation.
Check power supply wire size.
Check compressor starting.
Check 24 vac and unit transformer tap for correct power supply voltage.
X
X
Over voltage
Check power supply voltage and 24 vac before and during operation.
Check 24 vac and unit transformer tap for correct power supply voltage.
Performance Monitor —
Code 8
X
Heating mode FP2>125
 F
Check for poor airflow or overcharged unit.
X
Cooling mode FP1>125
 F 
OR FP2< 40
 F
Check for poor water flow or airflow.
FP1 and FP2 
Thermistors — 
Code 9
X
FP1 temperature is higher 
than FP2 temperature.
Swap FP1 and FP2 thermistors.
X
FP2 temperature is higher 
than FP1 temperature.
Swap FP1 and FP2 thermistors.
No Fault Code Shown
X
X
No compressor operation
See scroll compressor rotation section.
X
X
Compressor overload
Check and replace if necessary.
X
X
Control board
Reset power and check operation.
Unit Short Cycles
X
X
Dirty air filter
Check and clean air filter.
X
X
Unit in 'Test Mode'
Reset power or wait 20 minutes for auto exit.
X
X
Unit selection
Unit may be oversized for space. Check sizing for actual load of space.
X
X
Compressor overload
Check and replace if necessary.
Only Fan Runs
X
X
Thermostat position
Ensure thermostat set for heating or cooling operation.
X
X
Unit locked out
Check for lockout codes. Reset power.
X
X
Compressor overload
Check compressor overload. Replace if necessary.
X
X
Thermostat wiring
Check Y and W wiring at heat pump. Jumper Y and R for compressor 
operation in Test mode.