30RA/30RH
GB - 14
Troubleshooting
A list of possible faults, as well as the probable cause and
suggested solutions is shown as follows. In the event of a unit
malfunction it is recommended to disconnect the power supply and
ascertain the cause.
Symptoms
Cause
REMEDY
Unit does not start:
- No power supply;
CONNECT
 
POWER
 
SUPPLY
.
- Main switch open;
CLOSE
 
SWITCH
.
- Low line voltage;
CHECK
 
VOLTAGE
 
AND
 
REMEDY
 
THE
 
DEFICIENCY
.
- A protection has tripped;
RESET
.
- Contactor stuck open;
CHECK
 
AND
 
IF
 
NECESSARY
 
REPLACE
 
CONTACTOR
.
- Seized compressor;
CHECK
 
AND
 
IF
 
NECESSARY
 
REPLACE
 
COMPRESSOR
.
- Loose electrical connections;
CHECK
 
CONNECTIONS
.
Unit runs continuously or starts and stops frequently:
- Defective compressor contactor;
-
CHECK
 
AND
 
IF
 
NECESSARY
 
REPLACE
 
CONTACTOR
.
- Defective compressor;
CHECK
 
AND
 
IF
 
NECESSARY
 
REPLACE
 
COMPRESSOR
.
- Refrigerant losses;
CHECK
 
AND
 
ADD
 
THE
 
NECESSARY
 
QUANTITY
.
- Total water flow too low
CHECK
 
FOR
 
PRESSURE
 
DROP
 
IN
 
THE
 
HYDRAULIC
 
CIRCUIT
.
-
Static pressure in the hydraulic circuit  too low;
CHECK
 
IT
 
ON
 
THE
 
PRESSURE
 
GAUGE
 
AND
 
RESTORE
 
IT
 
IF
 
NECESSARY
.
Unit continuously cuts out at low pressure:
- Refrigerant losses;
CHECK
 
AND
 
ADD
 
THE
 
NECESSARY
 
QUANTITY
.
- Low water flow in the exchanger;
CHECK
 
WATER
 
PUMP
.
- Unit start-up delay;
WAIT
 
UNTIL
 
THE
 
SYSTEM
 
HAS
 
STABILISED
.
Unit continuously cuts out at high pressure:
- Defective high pressurestat;
CHECK
 
AND
 
IF
 
NECESSARY
 
REPLACE
 
PRESSURESTAT
.
- Blocked expansion valve;
CHECK
 
AND
 
REPLACE
 
IF
 
NECESSARY
.
- Blocked filter drier;
CHECK
 
AND
 
IF
 
NECESSARY
 
REPLACE
 
FILTER
.
- The outdoor fan/s does/do not work;
CHECK
 
THE
 
CONDITION
 
OF
 
THE
 
FAN
 
MOTOR
/
S
 
AND
 
ITS
/
THEIR
 
ELECTRICAL
CONNECTIONS
.
-
Obstructed or dirty battery;
REMOVE
 
THE
 
OBSTRUCTION
 
OR
 
CLEAN
 
THE
 
BATTERY
.
Abnormal system noise:
- Piping vibration;
SUPPORT
 
PIPING
.
- Noisy compressor;
CHECK
 
AND
 
CHANGE
 
IF
 
NECESSARY
.
- Hissing expansion valve;
CHECK
 
AND
 
ADD
 
REFRIGERANT
 
IF
 
NECESSARY
.
- Badly fitting panels;
INSTALL
 
CORRECTLY
.
Compressor loses oil:
- Leaking refrigeration circuit;
REPAIR
 
LEAK
.
Water loss:
- Defective entering or leaving connections;
CHECK
 
AND
 
TIGHTEN
 
IF
 
NECESSARY
.
The unit does not defrost
(only for 30RH units):
- Four-way reversing valve faulty;
CHECK
 
AND
 
REPLACE
 
THE
 
VALVE
 
IF
 
NECESSARY
.
- Defrost sensor broken;
CHECK
 
AND
 
REPLACE
 
THE
 
SENSOR
 
IF
 
NECESSARY
.