Справочник Пользователя для Carrier 30RA

Скачать
Страница из 16
GB - 3
30RH
E N G L I S H
30RH
017
021
026
033
Power supply
V-ph-Hz
400-3-50 / 400-3-50+N
Voltage range
V
360-440
Nominal power input*
kW
6.21
7.95
9.13
11.83
Effective power input**
kW
6.30
8.10
9.30
12.00
Nominal current drawn*
A
10.75
14.80
18.70
23.65
Effective current drawn**
A
10.90
15.05
19.05
24.00
Maximum power drawn***
kW
7.87
10.8
12.23
14.95
Maximum current drawn***
A
13.50
20.00
22.50
28.00
Starting current
A
87
132
134
139
Pump power input
kW
0.65
0.68
0.89
0.93
*
Based on an outdoor entering air temperature of 35 
°
C db, an evaporator entering water temperature of 12 
°
C and an evaporator leaving water temperature of 7 
°
C, unit without hydronic
module
** The power and current values indicated refer to Eurovent Standard conditions.
*** The power and current values indicated refer to an evaporator leaving water temperature of 10 
°
C and a condenser entering air temperature of 46 
°
 C.
Table II: Electrical data - Model RH
30RH
017
021
026
033
Net cooling capacity*
kW
16.70
21.60
24.60
29.00
Net heating capacity**
kW
18.80
24.80
27.80
34.00
Operating weight
without hydronic module
kg
235
265
285
315
with hydronic module
kg
255
285
315
345
Refrigerant charge  R-407C
kg
7.15
7.84
9.30
11.00
Compressor
One scroll compressor
Control system
Pro Dialog-Plus
Refrigerant-water heat exchanger
One plate heat exchanger
Net water volume
l
1.50
1.88
2.16
2.82
Water connections  (MPT gas)
inches
1
1
1-1/4
1-1/4
Maximum water pressure
kPa
1000
1000
1000
1000
(unit without hydronic module)
Hydronic module
Pump, mesh filter, expansion tank, flow switch, pressure gauges, automatic air purge valve and drain plug,
flow control valve and safety valve.
Pump
One single-speed pump
Available pressure***
kPa
142
125
155
149
Water inlet connection (MPT gas)
inches
1-1/4
1-1/4
1-1/4
1-1/4
Water outlet connection (MPT gas)
inches
1
1
1-1/4
1-1/4
Drain tap coupling (MPT gas)
inches
1/2
1/2
1/2
1/2
Closed expansion tank water volume
l
8
8
8
8
Water fill system (option)
Inlet/outlet diameter (MPT gas)
inches
1/2
1/2
1/2
1/2
Refrigerant-air heat exchanger
One, copper tubes and aluminium fins
Tube diameter
inches
3/8
3/8
3/8
3/8
No. of rows
3
2
3
4
Tubes/row
52
60
60
60
Fin spacing
mm
1.81
1.81
1.81
1.81
Fan
Two, axial type with two speeds
Diameter
mm
500
610
610
610
No. of blades
5
5
5
5
Air flow (high speed)
l/s
2222
3611
3111
3333
Fan speed (high speed)
r/s
12.83
10.83
11.67
11.83
*
*The ratings indicated refer to an evaporator entering/leaving temperature of 12/7 
°
C,and air entering the condenser at 35 
°
C.
**
The ratings indicated refer to a condenser entering/leaving temperature of 40/45 
°
C,and air entering the condenser at 7 
°
C d.b.and 6 
°
C w.b.
*** At nominal water flow rate during cooling.
Table I: Physical data - Model RH
Physical data and electrical data -  Model RH