(1) Press the 
TEST
 button for three seconds to 
activate the maintenance mode.
(2) Press the TEMP. 
 
 buttons to set the refrigerant address.
MAINTENANCE
(3)  Select the data you want to display.
MENU
ON/OFF
Compressor 
information
Cumulative 
operation time
ON/OFF 
number
Operation 
current
Display A
Display B
Display A
OUTDOOR UNIT
H·EXC. TEMP
OUTDOOR UNIT
OUTLET TEMP
OUTDOOR UNIT
OUTDOOR TEMP
Heat exchanger 
temperature
Comp discharge 
temperature
Outdoor ambient 
temperature
Display A
Outdoor unit 
information
INDOOR UNIT
INLET TEMP
INDOOR UNIT
H·EXC. TEMP
INDOOR UNIT
FILTER USE H
Indoor room 
temperature
Heat exchanger 
temperature
Filter operation 
time
Display A
Indoor unit 
information
* The filter operation time displayed is the number of hours the filter has been 
used since the filter reset was performed.
(4) Press the 
FILTER
 button.
(5) The data is displayed in C.
(Airflow temperature display example)
Flashing
Waiting for 
response
Approx. 
10 sec.
147°F
* Repeat steps (2) to (5) to check another date.
(6) Press the 
TEST
 button for three seconds or press the 
ON/OFF
 button 
to deactivate the maintenance mode.
Stable operation
  Using the maintenance mode, the operation frequency can be fixed and the 
operation can be stabilized. If the air conditioner is stopped, use the following 
procedure to start this operation.
COOL
STABLE MODE
HEAT
STABLE MODE
STABLE MODE
CANCEL
Stable cooling 
operation
Stable heating 
operation
Stable operation 
cancellation
Display A
Press the 
MODE
 button to select the operation mode.
Press the 
FILTER
 button.
Waiting for stable 
operation
Display D
Stable 
operation
10-20 min.
* You can check the data using steps (3) to (5) of the maintenance mode 
operation procedures while waiting for the stable operation.
8.  Easy maintenance function [This function only for A-control]
By using the maintenance mode, you can display many types of maintenance data 
on the remote controller such as the heat exchanger temperature and compressor 
current consumption for the indoor and outdoor units.
This function can be used whether the air conditioner is operating or not.
During air conditioner operation, data can be checked during either normal 
operation or maintenance mode stable operation.
*  This function cannot be used during the test run.
*  The availability of this function depends on the connecting outdoor unit. Refer to 
the brochures.
D
A
C
B
Display example (Comp discharge temperature 147°F)
Display C
Maintenance mode operation procedures
COMP ON
x10 HOURS
COMP ON
x100 TIMES
COMP ON
CURRENT (A)