Скачать
Страница из 14
3
2. Installation location
3. Installing the indoor unit
Fig. 2-1
3.1. Check the indoor unit accessories (Fig. 3-1)
The indoor unit should be supplied with the following accessories.
PARTNUMBER
ACCESSORY
QUANTITY
LOCATION OF SETTING
1
Wall-fixing bracket
1
Fix at the back of the unit
2
Tapping screw 4 
× 35
12
3
Insulation material
2
4
Band
4 (large) + 5 (small)
5
Felt tape
3
6
Drain socket
1
Set inside the unit
7
Wireless remote controller
1
8
Remote controller holder
1
9
Alkali batteries
2
0
Wired remote controller
1
for PKA-A·FA
q
Drain adaptor
1
2.1. Outline dimensions (Indoor unit) (Fig. 2-1)
Select a proper position allowing the following clearances for installation and mainte-
nance.
(inch)
Models
W
D
H
A
B
C
E
F
A24, A30
1400
235
340
Min. 150
Min. 50
Min. 30
Max. 250 Max. 150
55-1/8
9-1/4
13-3/8 Min. 5-15/16
Min. 2
Min. 1-3/16 Max. 10 Min. 5-15/16
A36
1680
235
340
Min. 150
Min. 50
Min. 30
Max. 250 Max. 150
66-5/32
9-1/4
13-3/8 Min. 5-15/16
Min. 2
Min. 1-3/16 Max. 10 Min. 5-15/16
 Warning:
Mount the indoor unit on a ceiling strong enough to withstand the weight of the
unit.
2.2. Outline dimensions (Outdoor unit)
Refer to the outdoor unit installation manual.
D
A
C
F
E
H
W
B
1
2
3
4
5
6
7
8
9
A
C
D
E
B
Fig. 3-1
Fig. 3-3
3.2. Installing the wall mounting fixture (Fig. 3-2)
1) Setting the wall mounting fixture and piping positions
Using the wall mounting fixture, determine the unit’s installation position
and the locations of the piping holes to be drilled.
 Warning:
Before drilling a hole in the wall, you must consult the building contractor.
A Indoor unit center line
B Left drain range
C Right drain range
D Hole for tapping screw
E Bolt hole
F Hole for tapping screw
G Contour of the unit
H Knockout hole for left rear piping
I Rear piping access hole (90-100 mm, 3-9/16 to 4 inch dia.)
2) Drilling the piping hole (Fig. 3-3)
Use a core drill to make a hole of 90-100 mm, 3-9/16 to 4 inch diameter in the
wall in the piping direction, at the position shown in the diagram to the left.
The hole should incline so that the outside opening is lower than the inside
opening.
Insert a sleeve (with a 90 mm, 3-9/16 inch diameter and purchased locally)
through the hole.
Note:
The purpose of the hole’s inclination is to promote drain flow.
A Sleeve
B Hole
C (Indoors)
D Wall
E (Outdoors)
(mm)
38-31/32
9-21/32
11-7/32
17-29/32
13/32
×3-19/32= (35-13/16)
3/4
13/32
7-1/4
11-1/32
2-3/8
1-3/16
1-3/16
1-3/16
1-5/32
3-
5/
32
3-5/32
35-7/16
3-19/32
3-17/32
24-1/32
12-3/8
11-1/32
9-7/16
8-27/32
23/32
23/32
A
B
C
G
I
H
F
E
D
50
35-7/16
3/4 
3-19/32
11-5/8
8-27/32
9-71/16
7-3/32
11-1/32
12-3/8
3-17/32
29-17/32
2-
3/
8
2-3/8
11-1/32
1-5/32
1-3/16
1-3/16
1-3/16
13/32
7-1/4
1/2
×3-19/32=(46-9/16)
9-21/32
11-7/32
23-7/16
I
H
H
E
D
B
G
A
C
F
23/32
23/32
7-3/32
7-3/32
3-
5/
32
3-5/32
(inch)
■ A24, A30
■ A36
Fig. 3-2
0
}
for PKA-A·FAL
7
7
7
7
7 - 9
9
9
9
9 are stored in a cut-out section of the packing material (styrofoam).
q