Справочник Пользователя для Mitsubishi Electronics PKA-AFA
3
2. Installation location
3. Installing the indoor unit
Fig. 2-1
3.1. Check the indoor unit accessories (Fig. 3-1)
The indoor unit should be supplied with the following accessories.
PARTNUMBER
ACCESSORY
QUANTITY
LOCATION OF SETTING
1
Wall-fixing bracket
1
Fix at the back of the unit
2
Tapping screw 4
× 35
12
3
Insulation material
2
4
Band
4 (large) + 5 (small)
5
Felt tape
3
6
Drain socket
1
Set inside the unit
7
Wireless remote controller
1
8
Remote controller holder
1
9
Alkali batteries
2
0
Wired remote controller
1
for PKA-A·FA
q
Drain adaptor
1
2.1. Outline dimensions (Indoor unit) (Fig. 2-1)
Select a proper position allowing the following clearances for installation and mainte-
nance.
nance.
(inch)
Models
W
D
H
A
B
C
E
F
A24, A30
1400
235
340
Min. 150
Min. 50
Min. 30
Max. 250 Max. 150
55-1/8
9-1/4
13-3/8 Min. 5-15/16
Min. 2
Min. 1-3/16 Max. 10 Min. 5-15/16
A36
1680
235
340
Min. 150
Min. 50
Min. 30
Max. 250 Max. 150
66-5/32
9-1/4
13-3/8 Min. 5-15/16
Min. 2
Min. 1-3/16 Max. 10 Min. 5-15/16
Warning:
Mount the indoor unit on a ceiling strong enough to withstand the weight of the
unit.
unit.
2.2. Outline dimensions (Outdoor unit)
Refer to the outdoor unit installation manual.
D
A
C
F
E
H
W
B
1
2
3
4
5
6
7
8
9
A
C
D
E
B
Fig. 3-1
Fig. 3-3
3.2. Installing the wall mounting fixture (Fig. 3-2)
1) Setting the wall mounting fixture and piping positions
s Using the wall mounting fixture, determine the unit’s installation position
s Using the wall mounting fixture, determine the unit’s installation position
and the locations of the piping holes to be drilled.
Warning:
Before drilling a hole in the wall, you must consult the building contractor.
A Indoor unit center line
B Left drain range
C Right drain range
D Hole for tapping screw
E Bolt hole
F Hole for tapping screw
G Contour of the unit
H Knockout hole for left rear piping
I Rear piping access hole (90-100 mm, 3-9/16 to 4 inch dia.)
B Left drain range
C Right drain range
D Hole for tapping screw
E Bolt hole
F Hole for tapping screw
G Contour of the unit
H Knockout hole for left rear piping
I Rear piping access hole (90-100 mm, 3-9/16 to 4 inch dia.)
2) Drilling the piping hole (Fig. 3-3)
s Use a core drill to make a hole of 90-100 mm, 3-9/16 to 4 inch diameter in the
s Use a core drill to make a hole of 90-100 mm, 3-9/16 to 4 inch diameter in the
wall in the piping direction, at the position shown in the diagram to the left.
s The hole should incline so that the outside opening is lower than the inside
opening.
s Insert a sleeve (with a 90 mm, 3-9/16 inch diameter and purchased locally)
through the hole.
Note:
The purpose of the hole’s inclination is to promote drain flow.
The purpose of the hole’s inclination is to promote drain flow.
A Sleeve
B Hole
C (Indoors)
D Wall
E (Outdoors)
B Hole
C (Indoors)
D Wall
E (Outdoors)
(mm)
38-31/32
9-21/32
11-7/32
17-29/32
13/32
×3-19/32= (35-13/16)
3/4
13/32
7-1/4
11-1/32
2-3/8
1-3/16
1-3/16
1-3/16
1-5/32
3-
5/
32
3-5/32
3-5/32
35-7/16
3-19/32
3-17/32
24-1/32
12-3/8
11-1/32
9-7/16
8-27/32
23/32
23/32
A
B
C
G
I
H
F
E
D
50
35-7/16
3/4
3-19/32
11-5/8
8-27/32
9-71/16
7-3/32
11-1/32
12-3/8
3-17/32
29-17/32
2-
3/
8
2-3/8
2-3/8
11-1/32
1-5/32
1-3/16
1-3/16
1-3/16
13/32
7-1/4
1/2
×3-19/32=(46-9/16)
9-21/32
11-7/32
23-7/16
I
H
H
E
D
B
G
A
C
F
23/32
23/32
7-3/32
7-3/32
3-
5/
32
3-5/32
3-5/32