VII  Control ] 
- 151 -
HWE09080
GB
(3)  P264, P288, P312, P336, P360 models <PQHY only>
*1  
Qj:Total capacity (model name) code
Initial startup mode starts. 
The compressor on the OC starts up.  
F     60Hz 
The total operating load of the indoor unit 
after 5 minutes of operation is P96 or above.
( *1     Qj     50)
The total operating load of the indoor unit after 
5 minutes of operation is between P96 and P400.
(50 < *1    Qj< 200)
50     F     60Hz (OC, OS1, and OS2)
or     F < 50Hz (OC, OS1, and OS2)
Completed in the integrated operation time of 35 minutes.
Completed in the integrated operation time of 90 minutes.
The compressor on the OS remains in operation, and the 
compressors on the OS1 and OS2 start up.
50     F     60Hz (both OC and OS1)
or      F < 50Hz (both OC and OS1)
Completed in the integrated operation time of 35 minutes.
Completed in the integrated operation time of 90 minutes.
The compressor on the OC remains in operation, 
and the compressor on the OS1 starts up.
50     F     60Hz (OC)
or      F < 50Hz (OC)
Completed in the integrated operation time of 35 minutes.
Completed in the integrated operation time of 90 minutes.
The compressor on the OC starts up. 
The OC, OS1, and OS2 stop. 
The startup sequence of the OC, 
OS1, and OS2 is rotated.
(The startup sequence of the OC, 
 OS1 and OS2 is changed.)
The OC, OS1, and OS2 stop.
The startup sequence of the OC, OS1, 
and OS2 is rotated.
(The startup sequence of the OC, 
 OS1 and OS2 is changed.)
The OC, OS1, and OS2 stop. 
The startup sequence of the OC, 
OS1, and OS2 is rotated.
(The startup sequence of the OC, 
 OS1 and OS2 is changed.)
50     F     60Hz (OS1)
or      F < 50Hz (OS1)
Completed in the integrated operation time of 35 minutes.
Completed in the integrated operation time of 90 minutes.
The compressor on the OS1 starts up. 
50     F     60Hz (OS2)
or      F < 50Hz (OS2)
Completed in the integrated operation time of 35 minutes.
Completed in the integrated operation time of 90 minutes.
The compressor on the OS2 starts up.  
*2
*3
*4
*5
Yes 
No
No 
Yes
Initial startup mode complete 
50     F     60Hz (both OS1 and OS2)
Completed in the integrated operation time of 35 minutes.
Completed in the integrated operation time of 90 minutes.
The compressor on the OS1 remains in operation, 
and the compressor on the OS2 starts up.
or      F < 50Hz (both OS1 and OS2)
*2
The air conditioning load is 
too small for the OC, OS1, 
and OS2 to simultaneously 
stay in operation.
*3
The air conditioning load is 
too small for both OC and 
OS1, or OS1 and OS2 to 
simultaneously stay in 
operation.
*4
The air conditioning load is 
high enough for OC, OS1 
and OS2 to simultaneously 
stay in operation.
*5
The air conditioning load is 
high enough for both OC 
and OS1, or OS1 and OS2 
to simultaneously stay in 
operation.