Справочник Пользователя для Mitsubishi Electronics P500YMF-C
–57–
1
Detects the outdoor air temperature.
2
Performs fan control, liquid level
heater control, opening settings of
LEV for oil return and other functions.
heater control, opening settings of
LEV for oil return and other functions.
Thermistor
R
0
= 15 k
Ω
B
1/80
= 3460
Rt =
15exp{3460( - )}
15exp{3460( - )}
0
°
C: 15 k
Ω
10
°
C: 9.7 k
Ω
20
°
C: 6.4 k
Ω
25
°
C: 5.3 k
Ω
30
°
C: 4.3 k
Ω
40
°
C: 3.1 k
Ω
Resistance check
TH6
(Outdoor
temperature)
(Outdoor
temperature)
TH7
(Pipe inlet
heat ex-
changer
temperature)
(Pipe inlet
heat ex-
changer
temperature)
Outdoor unit
Name
Code
(Function)
Inspection method
Application
Product code
Specification
1
273+t
1
273
1
273+t
1
273
1
273+t
1
273+120
1
273+t
1
323
Resistance check
TH3
TH4
(Liquid level
detection)
TH4
(Liquid level
detection)
TH5
(Pipe
temperature)
(Pipe
temperature)
Detects liquid level of refrigerant inside
accumulator using the differences
among TH2, TH3, TH4.
accumulator using the differences
among TH2, TH3, TH4.
1
Frequency control.
2
Controls defrosting during heating.
Resistance check
Conductivity test
using tester
using tester
TH10
1) Detects the compressor shell
temperature.
2) Provides compressor shell over-
heating protection.
Inverter cooling fan control using THHS
temperature.
temperature.
1
Capacity control of high/low
pressure bypass when starting and
stopping.
pressure bypass when starting and
stopping.
2
Discharge pressure rise suppression.
Switching of capacity control valve inside
No. 2 compressor (Switching between
full load operation and unload operation)
(only P500 YMF-C).
No. 2 compressor (Switching between
full load operation and unload operation)
(only P500 YMF-C).
Capacity control and controlling the rise
of high-pressure (Back-up of frequency
control).
of high-pressure (Back-up of frequency
control).
R
120
= 7.465 k
Ω
B
25/120
= 4057
Rt =
7.465exp
{4057( - )}
7.465exp
{4057( - )}
20
°
C: 250 k
Ω
70
°
C:
34 k
Ω
30
°
C: 160 k
Ω
80
°
C:
24 k
Ω
40
°
C: 104 k
Ω
90
°
C: 17.5 k
Ω
50
°
C: 70 k
Ω
100
°
C: 13.0 k
Ω
60
°
C: 48 k
Ω
110
°
C: 9.8 k
Ω
R
50
= 17 k
Ω
B
25/120
= 4170
Rt =
17exp {4170 ( - )}
17exp {4170 ( - )}
0
°
C: 181 k
Ω
10
°
C: 105 k
Ω
20
°
C: 64 k
Ω
25
°
C: 50 k
Ω
30
°
C: 40 k
Ω
40
°
C: 26 k
Ω
AC 220 to 240 V
Open : conducting
Close: not conducting
Open : conducting
Close: not conducting
AC 220 to 240 V
Close: conducting
Open : not conducting
Close: conducting
Open : not conducting
AC 220 to 240 V
Open : conducting
Close: not conducting
Open : conducting
Close: not conducting
THHS inverter
heat sink tem-
perature
heat sink tem-
perature
SV1
discharge-
suction
bypass
discharge-
suction
bypass
SV22
capacity
control (full
load)
capacity
control (full
load)
SV32
capacity
control
(unload)
capacity
control
(unload)
SV4a
discharge-
suction
bypass
discharge-
suction
bypass
TH9
Controls defrosfing during heating
1) Detects the CS circuit fluid tempera-
ture.
2) Calculates the refrigerant circulation
configuration.
R
0
= 15 k
Ω
B
1/80
= 3460
Rt =
15exp{3460( - )}
15exp{3460( - )}
0
°
C: 15 k
Ω
10
°
C: 9.7 k
Ω
20
°
C: 6.4 k
Ω
25
°
C: 5.3 k
Ω
30
°
C: 4.3 k
Ω
40
°
C: 3.1 k
Ω
Solenoid
valve
valve