3-4. HEAT DEFROSTING CONTROL
(1) Starting conditions of defrosting
When the following conditions a) ~ c) are satisfied, the defrosting starts.
a) The defrost thermistor reads 26.6°F (-3°C) or less.
b) The cumulative operation time of the compressor has reached any of the set values  (defrost interval: 40-150 min-
utes).
c) More than 5 minutes have passed since the start-up of the compressor. 
 The defrost interval is decided by the previous defrosting time. The next defrost interval extends or shortens 0-20 
minutes compared with the previous defrost interval.
(2) Releasing conditions of defrosting
Defrosting is released when any one of the following conditions is satisfied:
a) The defrost thermistor continues to read 50.7°F (10.4°C).
b) Defrosting time exceeds 10 minutes.
c) Any other mode than HEAT mode is set during defrosting.
3-5. DISCHARGE TEMPERATURE PROTECTION CONTROL
This protection controls the compressor ON/OFF and operation frequency according to temperature of the discharge tempera-
ture thermistor.
(1) Compressor ON/OFF
  When temperature of the discharge temperature thermistor exceeds 240.8°F (116°C), the control stops the compressor.
  When temperature of the discharge temperature thermistor is 176°F (80°C) (2A/3A30NA/2B)/ 212°F (100°C) (3A30NA-
1
/4A/3B/4B) or less, the controls starts the compressor.
(2) Compressor operation frequency
  When temperature of the discharge temperature thermistor is expected to be higher than 240.8°F (116°C), the control 
decreases 12 Hz from the current frequency.
  When temperature of the discharge temperature thermistor is expected to be higher than 231.8°F (111°C) and less than 
240.8°F (116°C), the control decreases 6 Hz from the current frequency.
  When temperature of the discharge temperature thermistor is expected to be higher than 219.2°F (104°C) and less than 
231.8°F (111°C), the control is set at the current frequency.
MXZ-3B24NA  MXZ-3B30NA  MXZ-4B36NA
Number of operating 
unit 
Capacity code 
COOL (Hz) 
DRY (Hz) 
HEAT (Hz) 
Min. Max. 
Min. Max. 
Defrost 
1
3,4
15
58
22
25
70
70
7
15
58
22
25
70
70
9,10
15
71
31
25
80
80
12
15
80
42
25
80
80
2
5 ~ 7 
25
80
35
35
80
80
8 ~ 10 
25
80
35
35
80
80
11 ~ 13 
25
80
35
35
80
80
14 ~ 16 
25
80
35
35
80
80
17 ~ 
25
80
52
35
80
80
3 (MXZ- 3B)
9 ~ 
52
80
52
39
80
80
3 (MXZ-4B)
9 ~ 
52
90
52
39
103
80
4 (MXZ-4B)
12 ~ 
62
90
70
52
113
80