- 13 -
4-3. Connecting the M-NET transmission lines
(1) Supplying power to the M-NET transmission line from the BAC-HD150
Connect the M-NET transmission lines and the power jumper as shown in the figure below.
(2) To not supply power to the M-NET transmission line from the BAC-HD150
Connect the M-NET transmission lines and the power jumper as shown in the figure below.
 CAUTION • In an air conditioner system has more than 1 Outdoor units, System controller receiving transmission power 
through TB7 on one of the Outdoor unit would have a risk that the connected Outdoor units failure would stop 
power supply to System controller, and disrupt the whole system.
M-NET
TB7
TB3
CN40
CN41
CN41
CN41
CN41
CN40
CN40
OFF
ON
ON
TB3
A B S
BM ADAPTER
(BAC-HD150)
Outdoor unit
 CAUTION • Connect the shield to the S terminal of TB3.
Insulate the cables with vinyl tape, except the part 
that connects to the ring terminal.
• Connect the power jumper of BAC-HD150 to 
CN40 (supplies power).
Connect the power jumper of the outdoor unit 
to CN41
 (does not supply power).
• Use the type of transmission lines specified, and 
connect them to the appropriate terminals. Secure 
the cables to keep undue force from being applied. 
Improper connections or failure to properly secure 
cables may result in overheating and fire.
M-NET 
transmission line 
(non-polarized)
Shield
Cable 
clamps
M-NET
TB7
TB3
CN40
CN40
CN40
TB3
A B S
CN41
CN40
CN40
OFF
ON
ON
CN41
CN41
CN41
Shield
Cable 
clamps
BM ADAPTER
(BAC-HD150)
Outdoor unit
 CAUTION • Connect the shield to the S terminal of TB3.
Insulate the cables with vinyl tape, except the part 
that connects to the ring terminal.
• Connect the power jumper of BAC-HD150 to 
CN41 (does not supply power at factory setting).
Connect the power jumper of the outdoor unit 
to CN41
 (does not supply power).
• Use the type of transmission lines specified, and 
connect them to the appropriate terminals. Secure 
the cables to keep undue force from being applied. 
Improper connections or failure to properly secure 
cables may result in overheating and fire.
Power supply unit (PAC-SC51KUA...etc)
M-NET 
transmission line 
(non-polarized)