Справочник Пользователя для Johnson Controls TCGF24

Скачать
Страница из 4
Johnson Controls Unitary Products
362564-UTD-B-0708
TABULAR DATA SHEET
Outdoor Split System Air Conditioner 2 Thru 5 Tons
MODELS: TCGF24* THRU 60
14.5 SEER – R-410A, 1 PHASE
 
All dimensions are in inches. They are subject to change 
without notice. Certified dimensions will be provided upon 
request.
Physical and Electrical Data
MODEL
TCGF24S41S1
TCGF30S41S1
TCGF36S41S1
TCGF42S41S1
TCGF48S41S1
TCGF60S41S1
Unit Supply Voltage
208-230V, 1
φ, 60Hz
Normal Voltage Range 
1
1. Rated in accordance with ARI Standard 110, utilization range “A”.
187  to 252
Minimum 
Circuit 
Ampacity
16.8 18.4 19.1 23.9 27.9 35.9 
Max. Overcurrent Device Amps 
2
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
25 30 30 40 45 60 
Min. Overcurrent Device Amps 
3
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
20 20 20 25 30 40 
Compressor 
Type 
Scroll Scroll Scroll Scroll Scroll Scroll 
Compressor 
Amps
Rated 
Load
12.8 14.1 14.1 17.9 21.1 27.5 
Locked 
Rotor
58 73 77 112 
115 
135 
Crankcase 
Heater
No No No No No No 
Fan Motor Amps Rated Load
.8 
.8 
1.5 
1.5 
1.5 
1.5 
Fan 
Diameter 
Inches
22 22 22 24 24 24 
Fan Motor
Rated 
HP
1/8 1/8 1/4 1/4 1/4 1/4 
Nominal 
RPM
1075 
1075 850 850 850 850 
Nominal 
CFM
2750 2800 3200 3600 3600 3700 
Coil
Face 
Area 
Sq. 
Ft.
13.1 17.4 17.4 20.0 21.4 24.0 
Rows 
Deep
1 1 1 1 1 1 
Fin 
Inches
23 23 23 23 23 23 
Liquid Line Set OD (Field Installed)
3/8 
3/8 
3/8 
3/8 
3/8 
3/8 
Vapor Line Set OD (Field Installed)
3/4 
3/4 
3/4 
7/8 
7/8 
1 1/8 
Unit Charge (Lbs. - Oz.) 
4
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 
15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
3 - 2 
3 - 7
3 - 10 
4 - 4 
4 - 9 
5 - 9 
Charge 
Per 
Foot, 
Oz.
0.62 0.62 0.62 0.67 0.67 0.75 
Operating 
Weight 
Lbs.
128 130 145 172 180 199 
B
C
A
Unit
Model
Dimensions
(Inches)
Refrigerant Connection
Service Valve Size
A
1
1. Including Fan Guard.
B
C
Liquid
Vapor
24
28
29
29
3/8”
3/4”
30
36
29
29
36
36
29
29
42
34
33.6
33.6
7/8”
48
36
33.6
33.6
60
40
33.6
33.6
7/8”
2