METERING DEVICE 
Capillary Tube Systems 
All  units  are  equipped  with  capillary  tube  metering 
devices. 
Checking for restricted capillary tubes. 
1.   Connect pressure gauges to unit. 
2.   Start the unit in the cooling mode. If after a few minutes
      of operation the pressures are normal, the check valve
      and the cooling capillary are not restricted.  
3.      Switch  the  unit  to  the  heating  mode  and  observe  the 
gauge  readings  after  a  few  minutes  running  time.  If  
the system pressure is lower than normal, the heating  
capillary is restricted. 
4.     If the operating pressures are lower than normal in both  
      the heating and cooling mode, the cooling capillary is
       restricted.  
Proper safety procedures must be followed, 
and proper protective clothing must be worn 
when working with a torch.
Failure to follow these procedures could 
result in moderate or serious injury.
WARNING
BURN HAZARD
HERMETIC COMPONENTS CHECK
One-way Check Valve 
(Heat Pump Models)    
CHECK VALVE 
A unique two-way check valve is used on the reverse cycle  
heat pumps. It is pressure operated and used to direct the 
fl ow  of  refrigerant  through  a  single  fi lter  drier  and  to  the 
proper  capillary  tube  during  either  the  heating  or  cooling 
cycle. 
NOTE: The slide (check) inside the valve is made of tefl on.  
Should  it  become  necessary  to  replace  the  check  valve,  
place  a  wet  cloth  around  the  valve  to  prevent  overheating  
during the brazing operation. 
CHECK VALVE OPERATION 
In the cooling mode of operation, high pressure liquid enters  
the check valve forcing the slide to close the opposite port 
(liquid line) to the indoor coil. Refer to refrigerant fl ow chart. 
This directs the refrigerant through the fi lter drier and cooling 
capillary tube to the indoor coil. 
In the heating mode of operation, high pressure refrigerant  
enters the check valve from the opposite direction, closing  
the  port  (liquid  line)  to  the  outdoor  coil. The  fl ow  path  of 
the  refrigerant is then through the fi lter drier and heating 
capillary to the outdoor coil. 
Failure of the slide in the check valve to seat properly in 
either mode of operation will cause fl ooding of the cooling 
coil. This is due to the refrigerant bypassing the heating or 
cooling capillary tube and entering the liquid line. 
COOLING MODE 
In  the  cooling  mode  of  operation,  liquid  refrigerant  from 
condenser  (liquid  line)  enters  the  cooling  check  valve 
forcing the heating check valve shut. The liquid refrigerant 
is directed  into the liquid dryer after which the refrigerant 
is metered  through cooling capillary tubes to evaporator. 
(Note:  liquid  refrigerant  will  also  be  directed  through  the 
heating  capillary  tubes  in  a  continuous  loop  during  the 
cooling mode). 
HEATING MODE 
In  the  heating  mode  of  operation,  liquid  refrigerant  from 
the  indoor coil enters the heating check valve forcing the 
cooling  check valve shut. The liquid refrigerant is directed 
into the  liquid dryer after which the refrigerant is metered 
through  the heating capillary tubes to outdoor coils. (Note: 
liquid refrigerant will also be directed through the cooling 
capillary  tubes  in  a  continuous  loop  during  the  heating 
mode). 
CUT/SEVER HAZARD 
WARNING
Be careful with the sharp edges and corners. 
Wear protective clothing and gloves, etc.
Failure to do so could result in serious injury.
33