All units shall be factory assembled, piped, wired and fully charged with 
310 for air conditioners and ARI standard 380 for heat pumps.  Units 
shall be UL listed and carry a UL label.  All units shall be factory run-
tested to check operation and be Friedrich or equivalent.
The basic unit shall not exceed 16” high x 42” wide.  Overall depth 
of  the  unit  from  the  rear  of  the  Friedrich  wall  sleeve  to  the  front  of 
the decorative front cover shall not exceed 21 ¼”.  The unit shall be 
designed so that room intrusion may be as little as 7 ½”.  Installations 
in walls deeper than 13 ¼” may be accomplished with the use of a 
deep wall sleeve (PDXWSEXT). Unit shall draw in ambient air through 
both sides of an outdoor architectural louver or grille measuring 42” 
  
.
r
e
v
u
o
l
 
e
h
t
 
f
o
 
n
o
i
t
r
o
p
 
e
l
d
d
i
m
 
t
u
o
 
r
i
a
 
t
s
u
a
h
x
e
 
ll
a
h
s
 
d
n
a
 
h
g
i
h
 
6
1
 
x
 
e
d
i
w
The architectural louver and wall sleeve shall be designed so that the 
louver may be installed from the inside of the building.  
REFRIGERATION SYSTEM – The refrigeration system shall be her-
metically sealed and consist of a rotary compressor that is externally 
mounted on vibration isolators no smaller than 1 3/8” dia. x 1 ½” high; 
condenser  and  evaporator  coils  constructed  of  copper  tubes  and 
  
.
e
t
a
s
n
e
d
n
o
c
 
f
o
 
s
n
o
ll
a
g
 
½
 
1
 
g
n
i
n
i
a
t
e
r
 
f
o
 
e
l
b
a
p
a
c
 
n
a
p
 
n
i
a
r
d
 
a
 
e
v
a
h
 
d
n
a
A tertiary condensate removal system shall also be incorporated for 
of the building as a safeguard against damage to the interior room.
INDOOR AIR HANDLING SECTION – The indoor air handling sec-
tion shall consist of a tangential blower wheel direct driven by a totally 
enclosed motor.  The air handling system shall be designed to minimize 
fan must have three fan speeds that may be selected by the user.
throughout the room.  The grille shall be reversible to allow a change 
personal injury or damage to the unit.
and reusable by cleaning with water or by vacuuming. 
The chassis shall have a built-in damper capable of providing at least 
damper closed to ensure a proper seal.
OUTDOOR  AIR  HANDLING  SECTION  –  The  outdoor  air  section 
shall consist of a single injection molded fan shroud that incorporates 
the outdoor motor mount into a single piece for ease of service and 
assembly.  The outdoor motor shall be totally enclosed, ball-bearing, 
permanently lubricated and directly drive the outdoor fan/slinger ring.
CONTROLS – Covered controls shall be accessible in a compartment 
at least  7½” wide with the controls no deeper than 1 ¼” in the opening 
to facilitate easy operation of the unit.  
The unit controls shall feature a soft blue LED readout that can display 
either room temperature or setpoint temperature.  The unit shall re-
ceive input from the digital control panel through push buttons labeled: 
‘Cool’, ‘Heat’, ‘High Fan’, ‘Med Fan’, ‘Low Fan’, 
‡
 ’, ‘
ˆ
’ and ‘Power’. 
When  ‘Off’, the unit may be put directly into cooling or heating mode 
by pressing the ‘Cool’ or ‘Heat’ button.  
The  unit  must  have  the  following  energy  saving  and  convenience 
features built-in:
• Quiet start/stop fan delay 
• Fan cycle control for cooling and heating independently
• Room freeze protection
• Random compressor restart
• Electronic temperature limiting
The PTAC must also offer the ability to be controlled by a remote wall-
mounted thermostat without additional accessories.  Low voltage inputs 
will include: C (common), R (24V power), Y (cooling), GL (fan low), GH 
(fan high), W (heat) and O (reversing valve on PDH heat pumps only).
PTAC models shall use a single stage cool / single stage heat ther-
mostat.  PTHP models shall use a single stage cool / two-stage heat 
thermostat.    An  accessory  thermostat  must  be  available  from  the 
manufacturer,  RT6  or  equivalent.    The  RT6  thermostat  will  provide 
  
.
s
e
d
o
m
 
n
a
f
 
d
n
a
 
t
a
e
h
 
,
l
o
o
c
 
m
o
r
f
 
n
o
i
t
c
e
l
e
s
 
e
d
o
m
 
,
t
n
i
o
p
t
e
s
 
e
r
u
t
a
r
e
p
m
e
t
The thermostat must also allow the selection of fan speed between 
high and low speed.
Other controls accessible without removal of the chassis shall include 
fan cycle switch, fresh air vent control and emergency heat override 
switch (heat pump only).
ELECTRICAL CONNECTION – All PTAC/PTHP units shall come from 
the factory with a power cord installed.  All 230/208V power cords shall 
feature a leakage current detection device on the plug head.  All units 
shall  feature  a  6-pin  connector  for  removal  of  the  power  cord.  The 
power cord shall be interchangeable to allow changes to the heater 
output based on the property/electrical requirements. 
GENERAL CONSTRUCTION – The wall sleeve shall be constructed 
of  18-gauge  Galvanized  zinc-coated  steel.    It  shall  be  prepared  by 
a  process  where  it  is  zinc  phosphate  pretreated  and  sealed  with  a 
cured  for  durability.    The  sleeve  shall  be  shipped  with  a  protective 
weatherboard and a structural center support, and be insulated for 
shipped  separately  and  made  from  stamped  or  extruded  anodized 
aluminum.  All louvers shall be in the horizontal plane. 
clips.  As an option the cover may be attached by two screws to pre-
vent tampering.  The front panel will feature a contoured discharge 
with no sharp corners. 
CORROSION PROTECTION – The unit shall have corrosion-resistant 
fans, fan shroud and drain pan for corrosion protection and to prevent 
rust on the side of the building below the outdoor louver. The unit shall 
-
rioration.  The outdoor coil shall have Diamonblue corrosion protection 
applications including seacoast environments.  All outdoor coils shall 
also have stainless steel endplates to eliminate rusting of the endplates.
WARRANTY – The warranty is one year on all parts and 5 years on 
the sealed system including compressor, indoor and outdoor coils and 
refrigerant tubing.
Cooling:   7600 – 15,000 Btuh
Heating:   7600 – 14500 Btuh (Heat Pump)
 
 6824 – 17060  Btuh (Electric Heat)
Friedrich Models:  PDE – Cooling with or without electric heat
 
 PDH – Heat Pump with electric heat